Step
Remove screw fixing the water baffle (fixing pipe);
remove screws fixing the tube clip, then remove the
water baffle(fixing pipe).
9.Remove Magnet Coil
Remove bolt fixing the magnet coil and then remove the
magnet coil.
10.Remove Capillary Sub-assy
Cut the cable tie and remove the fixed block of tube.
Unsolder the welding joint between the capillary sub-
assy and then remove the capillary sub-assy.
Note:
1.Before unsoldering the welding joint, please make
sure the refrigerant is discharged completely.
2.Before unsoldering the welding joint of capillary,
wrap the capillary with a wet cloth completely to avoid
damage to the capillary caused by high temperature.
Seal the discharge pipe port and suction pipe port of
compressor with rubber plug or rubber paper to avoid
impurities getting into the pipe.
46
Procedure
Screw
Magnet Coil
Bolt
Capillary Sub-assy
Junction
Tube Clip
Screws
Installation and Maintenance