Start up
­ Setting data table ­ Air regulation
NOZZLE
gph
spry
1,50
60°
1,65
60°
1,75
60°
2,00
60°
2,25
60°
2,50
60°
2,75
60°
3,00
60°
3,50
60°
4,00
60°
The settings above are basic settings.
These adjustment values are normally
suitable for commissioning the burner.
These values have been determined in
our test labs and are useful for the first
A
A
MIN
14
www.ecoflam­burners.com
PUMP
OUTPUT
bar
kg/h
12
6,2
12
7,0
12
7,6
12
8,3
12
9,3
12
10,4
12
11,5
12
12,5
12
14,9
11
16,0
switch-on as final setting must be done
using a combustion analyzer.
Favourable combustion values can be
achieved using the following nozzles:
B
Risk of air blast!
!
Continuously check CO, CO 2 and soot emissions when adjusting the output of
the burner. Optimise combustion values in the event of CO formation. CO must
not exceed 50 ppm.
MAX
FIRING HEAD SETTING
Pos.
0
1
2
2,5
3
3,5
4
4,5
5
5
Air damper setting (A).
Unscrew the fixing screw with the hexago-
nal spanner:
• turn the air damper clockwise, to reduce
output.
• turn the air damper counterclockwise
, to increase output.
Reached the desired value to fix the
screw.
Firing head setting (B).
To act on the screw in figure:
• turn Allen key till you reach the
requested value (index 0-5).
AIR DAMPER SETTING
Pos.
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
420010617900