Control Power Transformer - Toshiba JK Series Instructions Manual

Medium voltage controllers, 7.2kv maximum
Hide thumbs Also See for JK Series:
Table of Contents

Advertisement

Page 18
F .

Control Power Transformer

A control power transformer (Fig. 18) is
mounted on the left-hand side wall of the
controller
compartment.
t h e f u s e d p r i m a r y o f t h e c o n t r o l p o w e r
transformer from stabs on the withdrawable
contactor
carriage.
These stabs engage clips
on
the
transformer
inserted
into
the
compartment.
Optionally, a second transformer (Fig.
normally
used
as
an
can be mounted in the compartment. When
this option is supplied, a third set of stabs is
furnished on the withdrawable carriage. The
two transformers are then connected in an
open-delta
arrangement.
Another option sometimes supplied is a second
control power transformer connected in parallel
with the first to increase the available KVA
capacity.
B o t h t h e c o n t r o l a n d o p t i o n a l p o t e n t i a l
transformer are used to supply power to the
low voltage circuits of the controller. This
includes
power
for
operating coil and for various instrumentation.
An
electrical
interlock
that all load is disconnected from the control
power transformer secondary winding before
the power isolation switch can be opened or
closed.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Power
is
supplied
when
the
carriage
instrument
transformer,
the
vacuum
contactor
is
provided
to
ensure
GENERAL DESCRIPTION
to
is
Fig. 18 Control Power Transformer