INSTALLATION INTO A MASONRY FIREPLACE
Preparation
Measure your hearth to ensure it is large enough to accept the unit.
Unit must have a 36" clearance from the top of the stove to a mantel in accordance with NFPA 211.
For the USA: Hearth must extend at least
16 in. from the front of the fuel opening.
For Canada: Hearth must extend at least 18 in.
(450.0 mm) from the front of the fuel opening.
Inspect your hearth to be sure it is
constructed of a noncombustible material
such as brick or
stone. Do not install this stove on a hearth
that is constructed of wood framework that is
covered
by brick or stone and do not install this unit
in a zero (0) clearance fireplace. The
manufacturer will
not be held responsible for an accident
resulting from this stove being installed on a
hearth
constructed of a combustible material.
Inspect your fireplace to ensure it is in
proper working order and free of any
obstructions.
Prior to installation, remove the existing
damper or wire it to fasten it open.
Venting Your Stove - Direct Connect
When this unit is direct connected it will
require six inch (6") diameter 24 gauge pipe
from the stove through the damper opening.
(NOTE: The chimney connector must be
attached to the appliance
with a minimum of three (3) screws, and 3
screws should be used to attach each
adjoining section.)
We highly recommend having the chimney
fully lined with a 6 inch liner to ensure proper
draft. This will make it necessary to block off
the open area on both sides of the pipe that
passes through the damper opening, which
can be done with sheet metal or by packing
flame retardant fiberglass insulation in the
open areas (no paper or combustibles). You
must be sure the draft from the chimney is
being pulled through the stove, and not around the connector pipe. . We highly recommend you have this
done by a professional. You should also contact your local authorities to be sure you are following all codes.
Page | 14
INSTALLATION 
The 10‐3‐2 Rule: The chimney system must terminate 3.0 ft. 
above the point where its centerline passes through the roof 
AND the chimney must terminate 2.0 ft. above any part of the 
dwelling within a 10 ft. radius of the chimney. 
Remove or wire 
damper open 
36 in. (91.4 cm) minimum 
Stovetop to mantel 
See hearth requirements 
6 in. (15.24 cm) liner 
highly recommended 
Connector 
Pipe 