P/N 0535974_R
5 . Ensure that drip piping is supported to relieve
any stress on drip pipe connectors and waste
outlet hub . Drip piping MUST be supported
no more than 24 in . from waste outlet tee .
6 . Provide a suitable air break between
flood rim of the floor waste outlet and
outlet of drip pipe . To meet code on
low base merchandisers, it may be nec-
essary to install a field-supplied drip
pipe reducer .
An alternative is to cut the last
section of drip pipe at an angle .
Flush Floor Drip Piping Example for Ultra Low Front Cases
Liner EXT Front
to bottom of elbow)
Elbow is to be oriented toward rear of
case. Install elbow to tee, place elbow on
hub. Push elbow until it meets the liner.
B
Elbow
Tee
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
5.35
.17
DETAIL B
Hub-Drain
Right Side Partial View
(Case end removed
for clarity)
DETAIL A
7 . Prevent drip pipes from freezing:
Do not install drip pipes in contact with
uninsulated suction lines . Suction lines
should be insulated with a nonabsorbent
insulation material .
Where drip pipes are located in dead air
spaces, such as between merchandisers or
between a merchandiser and a store wall,
provide means to prevent freezing .
Liner EXT Front
to bottom of elbow)
Liner
0547545
B
Right Side Partial View
B
(Case end removed
for clarity)
5.35
DETAIL B
Hub-Drain
Elbow
Tee
DETAIL A
Medium Temperature
3-3
.17
Liner
Liner EX
to bottom
Merchandisers