Filter Change On The Filterbox - Bosch FAS-420-TM-R Operation Manual

Aspiration smoke detector lsn improved
Hide thumbs Also See for FAS-420-TM-R:
Table of Contents

Advertisement

84
en | Maintenance
8.6

Filter Change on the Filterbox

Changing the filter inserts (in fig.: FAS‑ASD‑FL Filterbox Large)
To replace the filter inserts, proceed as follows:
1.
2.
Notice!
In applications with largely fine dust build-up, three fine dust filters can also be used (subject
to separate order).
Notice!
Opening the housing cover of the filterbox causes an airflow malfunction in the FAS-420-TM.
2020.04 | 5.1 | F.01U.088.878
1.
A B
C
2.
Remove the four screws and remove the housing cover.
Remove the old filter inserts and clean the inside of the housing carefully to remove dust.
Now fit the cleaned or new filter inserts. When using the spare filter set for the large
filterbox, ensure you follow the correct sequence (see label on base of housing).
Replace the housing cover and screw it back on.
Operation guide
Aspiration smoke detector LSN improved
A
Primary filter
B Coarse dust filter
C Fine dust filter
Bosch Sicherheitssysteme GmbH

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fas-420-tmFas-420-tm seriesFas-420-tm-rvb

Table of Contents