3.5 Commissioning

3.5.1 Procedure

1. Turn on the air supply to the positioner.
2. Connect the bus with arbitrary polarity (or auxiliary power 9 V DC ... 32 V DC)
to the bus terminals.
conf
3. Check for proper mounting:
-
Press and hold
has run down from 3 to 0, then release
level (mode 1.x) is reached and indicated.
-
Press and hold
-
Additionally briefly press
sensor range) is displayed.
-
Release
-
Press
and note the values. The angle of rotation is indicated in degrees.
Recommended range:
between -28° and +28° for linear actuators
between -57° and +57° for rotary actuators
Minimum angle: 25°
IMPORTANT
4. Return to the remote level.
-
Press and hold
-
Wait until the countdown has run down from 3 to 0, then release
ENTER
conf
26
Important
The prerequisite for proper operation of the TZIDC-220 positioner on the
bus is that the Transducer Block can change over to AUTO mode. This
requires that the operating range of both the positioner and the valve be
matched to each other (as described in step 5 of the procedure below). If
this auto-adjustment should fail or cannot be performed for any reason,
the Transducer Block remains in "Out of Service" mode and the configu-
ration bit in the "BLOCK-ERR Parameter" is "active".
°
C
%
mA
is displayed.
M
and
ODE
.
MODE
.
MODE
or
to move the actuator to its mechanical limit stops in both directions,
The positioner should be mounted/adjusted in such a way that the por-
tions of the sensor's operating range above and below the center point
are nearly identical. Make sure to use the rotation angle of the position
sensor in the positioner to its utmost extent. Refer to chapter 3.1 "Me-
chanical mounting" for details about how to readjust/correct if required.
and
MODE
.
°
C
%
is displayed.
mA
Electro-pneumatic positioner TZIDC-220
E
simultaneously. Wait until the countdown
NTER
M
ODE
or
until mode 1.3 (manual adjustment within the
.
ENTER
E
.
and
The operating
NTER
MODE
and
42/18-82 EN