3. Mount the lever and the angle bracket to the positioner
5
Fig. 7
Mounting lever and angle bracket to TZIDC-220
Attach the lever (1) to the positioner's feedback shaft (2) (can only be mounted in
one position due to the flat on the side of the feedback shaft).
Check whether the lever travels within the operating range (between the arrows) by
observing the arrow marks (3).
Hand-tighten the screw (4) at the lever.
Hold the preassembled positioner with the angle bracket (5) still loose in such a way
against the actuator that the follower pin on the lever introduces into the follower
guide, in order to determine the bore holes of the positioner to be used for the angle
bracket.
Fasten the angle bracket (5) with screws (6), and plain washers (7) to the corre-
sponding bore holes in the positioner case; if possible, tighten the screws evenly to
ensure linearity during operation. Align the angle bracket in the oblong hole to
achieve a symmetrical operating range (between the arrow marks (3)).
14
7
6
4
1
Electro-pneumatic positioner TZIDC-220
2
3
42/18-82 EN