ABB TZIDC-220 Operating Instructions Manual page 62

Electro-pneumatic positioner for foundation fieldbus with flameproof enclosure
Hide thumbs Also See for TZIDC-220:
Table of Contents

Advertisement

TÜV NORD CERT GmbH & Co. KG
Am TÜV 1
D-30519 Hannover
Annexe to IECEx TUN 04.0015X
Page 2 of 3
Electrical data for type TZIDC-110, TZIDC-210, TZIDC-120 resp. TZIDC-220 with marking
Ex ia IIC T6
Input circuit
(terminals +11, -12 resp. +, -)
Voltage
Current
Power
Characteristic line
Local interface for
communication (LKS)
and programming interface (X5)
Optionally the following modules are allowed to be used:
Shutdown-switch-input
(terminals +51, -52
resp. +85, -86)
Mechanical digital feedback
(terminals Limit1 +51, -52
resp. Limit2 +41, -42)
The intrinsically safe circuits themselves are safe galvanically separated up to a voltage of 60 V. The
"Local interface for communication (LKS) and programming interface (X5)" is connected with the signal
circuit.
62
in type of protection "Intrinsic Safety"
only for the connection to a certified intrinsically safe circuit (e.g.
FISCO power supply) with the maximum values according to the
following table:
FISCO power supply
ia/ib for group IIB/IIC
17.5 V
380 mA
5.32 W
rectangular
For the connection to a programmer resp. a PC outside of the
explosive hazardous area.
in type of protection "Intrinsic Safety"
only for the connection to a certified intrinsically safe circuit with the
following maximum values:
U
= 30 V
i
effective internal capacitance:
The effective internal inductance is negligibly small.
in type of protection "Intrinsic Safety"
Maximum values see IEC Certificate No.
(proximity switches of the company Pepperl + Fuchs GmbH)
Electro-pneumatic positioner TZIDC-220
FISCO power supply
ia/ib for group IIB/IIC
17.5 V
360 mA
2.52 W
Trapezoidal
C
= 3.7 nF
i
TÜV NORD CERT
Ex ia IIC resp. Ex ib IIC
Barrier or power supply
ia/ib for group IIB/IIC
24 V
250 mA
1.2 W
linear
Ex ia IIC resp. Ex ib IIC
Ex ib IIC
42/18-82 EN

Advertisement

Table of Contents
loading