CONNECTING THE DC CABLES TO THE INVERTER
It is important to use suitable cable lengths and sizes to get the most out of your
inverter. Use of cable that is too thin or too long will result in voltage drop between
the battery and inverter, and may trigger low voltage warnings and inverter shutdowns.
It is recommended to place cable in corrugated conduit to protect from damage.
The following table lists suitable cable sizes for different cable lengths available
from Projecta.
Cable Length
IP2000
IP2000-24
IP3000
IP3000-24V2
1. Prepare all cable ends with cable lugs.
2. Install a circuit breaker or high current fuse and fuse holder in the positive line as close
to the battery as possible. The following fuse & fuse holder is available from Projecta
IP2000: P/No. IFB-250 (250A fuse and holder) 12 Volt
IP3000: P/No. IFB-350 (350A fuse and holder) 12 Volt
IP2000-24: P/No. IFB-150 (150A fuse and holder) 24 Volt
IP3000-24V2: P/No. IFB-200 (200A fuse and holder) 24 Volt
3. Make sure the inverter On/Off switch is turned OFF.
4. Connect the cables to the DC input terminals on the rear of the inverter.
The red terminal is positive (+) and the black terminal is negative (-).
a. Connect the positive cable to the inverter and battery positive terminals.
b. Connect the negative cable to the inverter and battery negative terminals.
5. The inverter is earthed through the negative DC input cable. Additional earthing
can be wired from the DC negative terminal.
FUSE
8
Cable Specifications
IWK6 (3m, 49mm
IWK3 (3m, 32mm
IWK8 (1.5m, 95mm
IWK9 (1.5m, 70mm
CORRUGATED CONDUIT
0–3m
)
2
)
2
)
2
)
2
3–6m
Not Recommended
6m, 64mm
2
Not Recommended
Not Recommended