In this installation scenario, you can mount
the devices on the wall.
f Position the device centrally on the
longer wall.
f Mount the device 0.5 m below the ceiling.
Rooms with slanted ceil-
ings (slope angle > 20°)
In rooms with ceiling slope angles of more
than 20° to the horizontal position, heat
pads can form in the ceiling peak that
impede the smoke entering the smoke
alarm device.
> 20°
Fig. 12
Rooms with slanted ceilings
Allowed
Not allowed
Operating Manual: FRWM200 - Smoke Alarm Device with Radio Link
EN
Note the following for locations in rooms
with slanted ceilings:
f Mount devices at least 0.5 m and at
a maximum of 1 m away from the
ceiling peak.
4.3 Rooms with slanted and
horizontal ceilings
> 20°
Fig. 13
Straight mounting surface at least
1 m long and 1 m wide
Allowed
Not allowed
> 1,00
1/2
1/2
55