Pedestal kit for fk09/fb09 and fk10/fb10, frequency converters
Hide thumbs Also See for iC7 Series:

Advertisement

Pedestal Kit for FK09/FB09 and FK10/FB10
Installation Guide
3.
Fasten 2 M5 screws through the back flange of the pedestal base into the flange on the lower end of the frequency con-
verter.
4.
To secure the frequency converter to the wall or mounting panel, fasten 2 M10 bolts (not supplied) in the mounting holes
at the top of the frequency converter. Use 1 bolt per mounting hole.
Illustration 3: Pedestal-to-Frequency Converter Mounting Points
1
M5 screw in back flange
2
M10 nut
2.6 Creating Cable Openings
The cable entry plate provides cable entry and cable termination points, and must be installed to maintain the IP21/Type 1 or IP54/
Type 12 protection rating. The cable entry plate is placed between the frequency converter cabinet and the pedestal. Reuse the
cable entry plate that is shipped with the frequency converter.
The cable entry plate can be installed from inside the frequency converter cabinet or before attaching the front cover and side
plates of the pedestal. To install the cable entry plate, use the following steps. Refer to
1.
Create cable entry holes in the plate using a sheet metal punch.
2.
Insert the cable entry plate using 1 of the following methods:
Danfoss A/S © 2022.03
Illustration
4.
AN371942906358en-000101 / 136R0256 | 5