Auxiliary Sensors - Hisense Hi-Therma Series Service Handbook

Air-to-water heat pump, split/integra outdoor unit, split indoor unit, integra indoor unit, monobloc
Hide thumbs Also See for Hi-Therma Series:
Table of Contents

Advertisement

Control function

10.10.3 Auxiliary sensors

The unit offers 7 Auxiliary sensors that can be configured as different function.
The configuration of this option should be done through the master controller.
Configuration →I/O →Auxiliary sensors.
Mark
Description
As1
Auxsensor1
As2
Auxsensor2
As3
Auxsensor3
As4
Auxsensor4
As5
Auxsensor5
As6
Auxsensor6
As7
Auxsensor7
Optional function can be configured.
Auxiliary
Mark
sensor code
00
No Function
01
Tow3
02
Tswp
03
Tsolar
04
Ta_ao
05
Tow2
06
duty
07
Room_amb1
08
Room_amb2
09
Room_amb3
10
Room_amb4
11
Room_amb5
12
Room_amb6
13
Room_amb7
14
TDHW1
Default Value
Terminals ON board
01
00~14
(Tow3)
03
00~14
(Tsolar)
02
00~14
Tswp
05
00~14
(Tow2)
14
00~14
(TDHW1)
07
00~14
(Room_amb1)
08
00~14
(Room_amb2)
-
This sensor is used in case to combine Unit with hydraulic separator to detect Hot water
temperature detection of hydraulic separator.
In case of combining Unit with swimming pool, this sensor is used to detect swimming pool
water temperature.
In case of combining Unit with solar panels, this sensor is used to Detect Hot water
temperature of solar panels.
Optional Second Outdoor Ambient Temperature sensor accessory can be connected to the Auxiliary
sensor in case that the heat pump is located in a non-suitable position for this
measurement.
When Water Cycle 2 is available, auxiliary sensor need be configured as function of "Tow2" to detect
outlet water temperature of Water Cycle 2.
Used to detect duty signal when duty signal control is Enabled, the duty signal type can be 0- 10V, 0-5V
or 10-20mA.
Rooms function on master controller is selected as room thermostat, and in this scenario, auxiliary sensor
can be configured as function of "Room_amb1...7", and can be selected as room temperature detection
of specific room.
Auxiliary temperature sensor to detect water temperature in the DHW tank of lower side.
Terminals ON board Terminal s ON PCB1
A1
On PCB4
A2
On PCB4
A3
On PCB4
A4
On PCB4
A5
On PCB4
A6
On PCB4
A7
On PCB4
Description
290
Specification ON
board
THM8
-
THM10
-
THM9
-
THM6
-
THM11
-
THM17
-
THM18
-