10.8.3 EC WP1 speed control

Inside EC WP1 can be controlled by PWM input signal (EC Water Pump).
The configuration of this option should be done through the master controller.
Configuration →Heat pump→Water pump configuration
Mark
Pump_mode
Operation Speed Mode
Space speed (heating and
Space_speed
cooling)
DHW_speed
DHW speed
SWP_speed
SWP Speed
(1) Speed of Inside EC WP1 can be controlled by PWM input signal (EC Water Pump) in 2 optional modes:
● Fixed speed selected by installer when [Pump_mode] set as [Fix].
● Variable speed by Water Inlet and Water Outlet temperature when [Pump_mode] set as [ΔT].
NOTE:
1. Variable speed is valid only during space heating/cooling operation. DHW operation and SWP operation always works
as Fixed speed.
(2) When EC WP1 works as [Fix] of [Pump_mode], Fixed speed value of WP1_speed is set by [Space_speed] during space
heating/cooling operation, [DHW_speed] during DHW operation and [SWP_speed] during SWP operation.
● Set Fixed speed value and PWM input signal
WP1_speed
Space_speed
DHW_speed
SWP_speed
%
space cooling
50
55
60
65
70
75
80
85
90
95
100
(3) When EC WP1 works as [ΔT] of [Pump_mode], Speed of WP1 is controlled by PWM input signal to achieve target value
of Water Inlet and Water Outlet temperature difference.
● space heating operation
5%≤PWM_in (n) ≤60%
Maximum value of Target outlet water
temperature (refer to 10.2.2.3)
55- 60ºC
45 -55ºC
25-45ºC
less than 25ºC
● space cooling operation
5%≤PWM_in (n) ≤18%
Target value of Water Inlet and Water Outlet temperature difference sets as 5 ºC.
Description
Default Value
44(2.0HP)
PWM_in %
space heating
18
60
18
54
18
49
18
43
18
37
18
32
18
26
15
21
11
15
8
10
5
5
Target value of Water Inlet and Water
Outlet temperature difference
Range
Fix
Fix/ΔT
100%
50-100%
100%
50-100%
100%
50-100%
model
60(2.5HP)
PWM_in %
space cooling
space heating
18
55
18
50
18
45
18
40
18
35
18
30
18
25
15
20
11
15
8
10
5
5
8 ºC
7 ºC
5 ºC
3 ºC
269
Control function
Steps
1
5
5
5
80(3.0HP)
PWM_in %
space cooling
space heating
14
50
14
45
14
41
14
36
14
31
14
27
14
22
14
18
11
13
8
9
5
5
Units
°C
%
%
%

Advertisement