Converting The Appliance To Different Gas Types; Setting The Gas/Air Ratio - Benchmark RD 532 combi Installation And Servicing

Table of Contents

Advertisement

7
Converting the appliance to
different gas types
The setting is factory sealed at maximum. Adjustment to
the rated heat input and min. heat input is not neces-
sary.
Checking the gas supply pressure
B Check the gas supply pressure at the gas supply
pressure testing point.
Natural gas appliances must not be oper-
i
ated if the gas supply pressure is below
18 mbar or above 24 mbar.
LPG appliances must not be operated if
the supply pressure is below or above
37 mbar.
Natural gas
• Appliances for natural gas type G20 are factory set
to Wobbe-Index 15 kWh/m
pressure and sealed.
6 720 611 451 GB (03.11)
3
and 20 mbar supply

Converting the appliance to different gas types

7.1

Setting the gas/air ratio

The gas/air ratio may only be adjusted on the
basis of a CO
measurement at max. heat output
2
and min. heat output using an electronic tester.
B Switch off the appliance at the master switch (O).
B Remove the outer case (see page 15, refer to
fig. 13).
B Switch on the appliance at the master switch (I).
B Unscrew sealing plug from flue gas testing
point (234). Refer to fig. 43.
B Insert testing probe about 135 mm into the flue gas
testing point and seal testing point.
234
Fig. 43
B Press and hold
button until the display shows – –.
The
button will light up.
6 720 610 332-32.1O
Fig. 44
B Turn the temperature control
shows 2.0 .
After a short delay, the current operating mode set-
ting will be displayed (0. = Normal mode).
6 720 610 332-60.1O
Fig. 45
6 720 610 599 - 01.TD
until the display
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zwb 7-32 rd 532

Table of Contents