Panasonic SE4D Series Instruction Manual page 71

Light curtain type 4
Table of Contents

Advertisement

<Timing chart>
ON
Muting
sensor A
OFF
ON
Muting
sensor B
OFF
ON
Muting
sensor C
OFF
ON
Muting
sensor D
OFF
ON
Muting function
OFF
Light
Light
received
received
Light
status
blocked
ON
Control output
(OSSD 1 / 2)
OFF
Note: This is when the muting lamp diagnosis function is valid. If the muting lamp does not light up even if 1 sec.
is passed, the muting function becomes invalid. When the muting lamp diagnosis function is invalid, the
muting function becomes valid 0.05 sec. after the input conditions of the muting sensor A (C) and B (D)
were satisfied.
<Reference>
● It is possible to set the muting function into invalid per beam channel respectively and to specify the
input order of the muting input A and B to be set into valid by using the handy controller (SE9Z-HC) (op-
tional).
● It is recommended that two muting lamps should be connected in parallel. In this case, take care not to
exceed 10W.
0.03 to under 3 sec.
0.05 to 1 sec. (Note)
14ms or less
70