Labelling; Dimensions And Weight; Installation; Startup - Emerson TARTARINI PS/79-1 Instruction Manual

Table of Contents

Advertisement

Type PS/79-1 and PS/79-2

Labelling

BOLOGNA ITALY
O.M.T.
MATRICOLA
SERIAL Nr.
ANNO
Note 2
YEAR
NORME ARMONIZ.
EN
HARMONIZED STD.
CLASSE DI PERDITA
LEAKAGE CLASS
CLASSE FUNZIONALE
Cg
FUNCTIONAL CLASS
FLUIDO GRUPPO
1
pmax
FLUID GROUP
Note 3
PS
Note 4
TS
°C
body
Figure 2. Label for Type PS/79-1 and PS/79-2 Pilots
Note 1: See "Characteristics"
Note 2: Year of Manufacture
Note 3: Class 1: -10 to 60°C
Class 2: -20 to 60°C
Note 4: See "Characteristics"

Dimensions and Weight

TYPE PS/79-1 AND PS/79-2 FULL RANGE WEIGHT: 2.5 KG
Figure 3. Type PS/79-1 and PS/79-2 Pilots Dimensions, mm
2
2
APPARECCHIO TIPO / DEVICE TYPE
Note 1
DN1
DN2
Wa
Wao
Wau
bar
pao
PS
-
1.5
bar
bar PT=
covers
145

Installation

a . Check that data on the pilot's plate are compatible
with actual working conditions .
b . Install in accordance with regulator
instruction manual .
bar
bar

Startup

bar
See the set-up and pilot adjustment instructions
bar
applying to the equipment where the pilot is
x PS bar

Periodic Checks

Slowly close the outlet slam-shut and check line
pressure between it and regulator . A slight increase
in pressure should be detected: this results from
overload due to closing, and is followed by pressure
stabilization . If, however, outlet pressure continues
to rise, then seal is defective . Check if leak is coming
from regulator or pilot, and service .

SEP Statement

Emerson Process declares this product
conforms to Pressure Equipment Directive (PED)
2014/68/EU Article 4 Section 3 were designed and
manufactured in accordance to the Sound Engineering
Practice (SEP) .
According to Article 4 Section 3, these "SEP" products
must not bear the CE marking .

ATEX Requirements

If the provisions of EN 12186 and
EN 12279, national regulations,
if any, and specific manufacturer
recommendations are not put into
practice before installation and if
purge by inert gas is not carried out
before equipment's start-up and shut-
down operations, a potential external
and internal explosive atmosphere
can be present in equipment and
gas pressure regulating/measuring
stations/installations.
WARNING
fitted .