2. Electrical Service Specifications
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
IMPORTANT:
A.
When fuses are used they must be dual element, time delay, current limiting, class RK1
NOTES:
or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or
National Electrical Codes to listed appliance amp draw data.
B.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw rating and type of
breaker used.
C.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
PHASE
VOLTAGE
208
240
380
400
416
460/480
575
* AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.
(Motor lead wire is recommended.)
**50 Hz versions of the 380, 400, and 416 volt dryers are manufactured 4-wire only (unless ordered special as 3-wire service).
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to either the backside of the upper control door or left side panel/wall area
behind the control door. In the case of 208 VAC or 240 VAC, the supply voltage
must match the electric service specifications of the data label exactly.
WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: Manufacturer reserves the right to make changes in specifications at any time without notice or
obligation.
CG115-25 (Gas/Steam)
APPROX.
WIRE
AMP DRAW
SERVICE
60 Hz
3ø
3
14.5
3ø
3
14.6
3ø
4**
3ø
4**
3ø
4**
3ø
3
7.8
3ø
3
5.8
MINIMUM
WIRE SIZE
50 Hz
--
*
16.4
*
--
8.7
*
--
8.5
*
--
8.4
*
--
*
--
*
25
FUSING
CIRCUIT
Dual Element
BREAKER
Time Delay
20
20
20-25
20-25
15
15
15
15
15
15
15
15
15
15
030503