Continental Girbau CG115-25 III Installation Manual page 21

Phase 7 with s.a.f.e. and dual timer
Table of Contents

Advertisement

a. Outside Ductwork Protection
1) To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward
should be installed where the exhaust exits the building. If the exhaust ductwork travels vertically
up through the roof, it should be protected from the weather by using a 180° turn to point the
opening downward. In either case, allow at least twice the diameter of the duct between the duct
opening and the nearest obstruction.
IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust
ductwork.
2. Single Dryer Venting
a. Horizontal Venting
When possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct
should be laid out in such a way that the ductwork travels as directly as possible to the outdoors with
as few turns as possible. It is suggested that the use of 90° turns in ducting be avoided; use 30° or 45°
angles instead. The shape of the exhaust ductwork is not critical so long as the minimum cross section
area is provided.
IMPORTANT: Minimum duct size for a gas, electric, or steam dryer is 14-inches (35.56 cm) for a
round duct or 12-1/2" by 12-1/2" (31.75 cm by 31.75 cm) for a square duct.
DUCT SIZE MUST NOT BE REDUCED ANYWHERE DOWNSTREAM
OF THE DRYER.
IMPORTANT: Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust
duct area must be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water
column (W.C.).