Balance Refrigerant Of The 2-Way, 3-Way Valves - Carrier 42/38KCR024713 Service Manual

Table of Contents

Advertisement

Service manual
7.7

Balance refrigerant of the 2-way, 3-way valves

Procedure:
Confirm that both the 2-way and 3-way valves are set to the open position.
Connect the charge set to the 3-way valve's service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05 to 0.1
Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than
0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will not be
necessary to apply a evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be discharged.
14

Advertisement

Table of Contents
loading

This manual is also suitable for:

42/38qcr024713

Table of Contents