System Settings; Hmi Settings - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Table 11: Non group settings
Parameter
Values (Range)
IP address
Mac address
3.1.6

System settings

Table 12: Non group settings
Parameter
Values (Range)
Rated frequency
1=50Hz
2=60Hz
Phase rotation
1=ABC
2=ACB
Blocking mode
1=Freeze timer
2=Block all
3=Block OPERATE
output
Bay name
IDMT Sat point
10...50
Frequency adaptivi-
0=Disable
ty
1=Enable
SMV Max Delay
0=2/2 ms
1=3/3 ms
2=5/4 ms
3=6/5 ms
4=7/6 ms
Test mode selec-
1=Local
tion
2=Local+Remote,
maintenance
3=Local+Remote,
all levels
4=Binary input
3.1.7

HMI Settings

REX640
Technical Manual
Unit
Step
Unit
Step
I/I>
1
Basic functions
Default
Description
192.168.0.254
IP address for front
port (fixed)
XX-XX-XX-XX-XX-XX Mac address for
front port
Default
Description
1=50Hz
Rated frequency of
the network
1=ABC
Phase rotation or-
der
1=Freeze timer
Behaviour for func-
tion BLOCK inputs
REX640
Bay name in system
50
Overcurrent IDMT
saturation point
0=Disable
Enabling frequency
adaptivity
1=3/3 ms
SMV Maximum al-
lowed delay
1=Local
Authority for re-
mote activation of
test mode
59