Symbols used Document ID This symbol on the front page of this instruction refers to the Docu- ment ID. By entering the Document ID on www.vega.com you will reach the document download. Information, note, tip: This symbol indicates helpful additional infor- mation and tips for successful work.
During work on and with the device, the required personal protective equipment must always be worn. Appropriate use VEGAMET 341 is a universal controller for connection of a 4 … 20 mA sensor. You can find detailed information about the area of application in chapter " Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
Safety instructions for Ex areas For applications in explosion-proof areas (Ex), only devices with cor- responding Ex approval may be used. Observe the Ex-specific safety instructions. These are an integral part of the operating instructions and are enclosed with every device with Ex approval. VEGAMET 341 • 4 … 20 mA...
The respective scope of delivery results from the order specification. Scope of this operating This operating instructions manual applies to the following instrument instructions versions: • Hardware version from 1.0.0 • Software version from 1.10.0 VEGAMET 341 • 4 … 20 mA...
Principle of operation Application area The controller VEGAMET 341 feeds the connected 4 … 20 mA sen- sor, processes the measured values and displays them. The built-in housing is ideal for mounting in the switching cabinet. A large display...
PACTware/DTM or the VEGA Tools app is recom- mended. An overview of the available applications and functions as well as their adjustment options can be found in the appendix.
Protected against solar radiation • Avoiding mechanical shock and vibration • Storage and transport Storage and transport temperature see chapter " Supplement - temperature Technical data - Ambient conditions" • Relative humidity 20 … 85 % VEGAMET 341 • 4 … 20 mA...
The required cut-out is 92 x 92 mm (3.63 x 3.63 in) according to IEC 61554. A VEGAMET 341 in Ex version is an auxiliary, intrinsically safe instru- ment and may not be installed in explosion-endangered areas.
The VEGAMET 341 can also be looped into the existing circuit like a normal ammeter. Note: With a VEGAMET 341 in Ex version, the passive input is not available. Connecting Connection technology The power supply and the inputs and outputs are connected via removable screw terminals. You can find information on the max. wire...
Passive input without sensor supply for four-wire sensor Two-wire sensor Four-wire sensor Voltage supply for four-wire sensor 2 mm sockets for connection of a VEGACONNECT/HART handheld Passive input not available for Ex version Passive input not available for Ex version VEGAMET 341 • 4 … 20 mA...
Output signals are set to failure, background lighting of the display lights red The current measured values are then displayed and transmitted to the outputs. The background lighting of the display changes to white. VEGAMET 341 • 4 … 20 mA...
However, unlike the Bluetooth access code, it must be re-entered for each unlock. When using the adjustment app or DTM, the stored device code is then suggested to the user for unlocking. VEGAMET 341 • 4 … 20 mA...
" PINs and Codes". This greatly simplifies the use of additional adjust- ment tools, as all Bluetooth access and device codes are automati- cally synchronized when connected to the " myVEGA" account VEGAMET 341 • 4 … 20 mA...
2 mm for direct connection of a VEGACONNECT or other HART modems. The adjustment of the con- nected sensor is carried out via the VEGA Tools app or via PACTware and appropriate DTM. VEGAMET 341 • 4 … 20 mA...
Bargraph measured value Active measured value indication Status display/back- The display is equipped with a background lighting for better visibility. ground lighting It serves simultaneously as a status display which is also visible from VEGAMET 341 • 4 … 20 mA...
Relay/current output settings Indication Description Basic settings Number of measured Number of displayed measured value indications value indications Measured value indi- Settings for the measured value displays, automatic cation change of the measured value display VEGAMET 341 • 4 … 20 mA...
Information: When using PACTware and the respective DTM or the VEGA Tools app, additional settings can be carried out which are not possible or only partly possible with the integrated display and adjustment unit.
Page 21
When using the display and adjustment unit, the adjustment unit is always " mA". When using PACTware/DTM or the VEGA Tools app, further units can be selected. If these have been activated, they are also shown in the display.
Page 22
The characteristics of the current output can be set to 0 … 20 mA, 4 … 20 mA or inverted. The reaction in case of failure can also be adapted to the requirements. The reference value you refer to can also be selected. VEGAMET 341 • 4 … 20 mA...
Page 23
In this menu item, the fail safe relay can be activat- ed or deactivated. If relay 3 is to be configured as an operating relay, it must still be activated as an operating relay after deactivation as a fail safe relay. This is done in menu item" Measuring point - Relay 3" VEGAMET 341 • 4 … 20 mA...
Page 24
" Access protection" Caution: With protected parameter adjustment, adjustment via the VEGA Tools app as well as PACTware/DTM and other systems is also blocked. You can find further details in chapter " Access protection". Reset With a reset to basic setting, all settings except the display language and the Bluetooth access code are reset to factory settings.
Page 25
The simulation is automatically terminated after approx. 60 minutes. Device-TAG You can assign an unambiguous name to VEGAMET 341 to the Device-TAG via DTM/VEGA Tools app. This function is recommended when several instruments are implemented and a good documenta- tion of larger systems is required.
• Operating system: Android 5.1 or newer • Bluetooth 4.0 LE or newer Download the VEGA Tools app from the " Apple App Store", " Goog- le Play Store" or " Baidu Store" to your smartphone or tablet. Connecting Connecting Start the VEGA Tools app and select the function "Setup".
The selected menu item, recognisable by the colour change, is dis- played in the right half. Fig. 10: Example of an app view - Setup adjustment Enter the requested parameters and confirm via the keyboard or the editing field. The settings are then active in the device. Close the app to terminate connection. VEGAMET 341 • 4 … 20 mA...
Enter Bluetooth access For authentication, enter in the next menu window the 6-digit code Bluetooth access code: You can find the code on the information sheet "PINs and Codes" in the device packaging: VEGAMET 341 • 4 … 20 mA...
DTMs are compiled in a DTM Collec- tion. The DTMs can also be integrated into other frame applications according to FDT standard. Fig. 11: Example of a DTM view - Adjustment VEGAMET 341 • 4 … 20 mA...
10 Applications and functions The controller contains already preset applications and functions, which can be easily adjusted by means of an application assistant via PACTware/DTM or the VEGA Tools app. The following applications/ functions are described here as examples. Level measurement in storage tanks with overfill protection/dry run •...
Page 31
Enter the measured value and unit (e.g. volume and m³) and the cor- responding scaling values for 100 % and 0 % (e.g. 100 m³, 0 m³). Configure relay First select the requested mode for the relay (" Overfill protection, dry run protection, switching window ON/OFF"). Also define the appro- VEGAMET 341 • 4 … 20 mA...
Page 32
OFF. The switching points are set as follows: • Relay 1: Switch-off point 90 %, switch-on point 85 % • Relay 2: Switch-off point 5 %, switch-on point 10 % Information: The switch-on and switch-off point of the relays must not be set to the same switching point because this would cause a continuous switch- ing on and off when this threshold is reached. To avoid this effect also with fluctuating medium surfaces, it is a good idea to set a difference (hysteresis) of 5 % between the switching points. VEGAMET 341 • 4 … 20 mA...
Symbol, activated pump control Relay 1 and 2 are assigned to the pump control Relay 3 is assigned to the pump control and signals failure Relay is free i.e. not assigned to the pump control VEGAMET 341 • 4 … 20 mA...
Page 34
This measure achieves an even utilization of the pumps and increases operational reliability. VEGAMET 341 • 4 … 20 mA...
Page 35
Fig. 15: Example of pump control 2 Option Dry weather pump Pump control 2/4 with dry weather pump is used to protect e.g. rain retention basins with different sized pumps against overfilling. Normally (in fair weather), a pump with low capacity (dry weather pump) is sufficient to maintain the level in the retention basin at a VEGAMET 341 • 4 … 20 mA...
Page 36
Which pump is switched on depends on the selected pump mode. If all pumps are already switched on, the pump remains switched on. VEGAMET 341 • 4 … 20 mA...
Page 37
90 % limit, pump 3 is also switched on. For relay 1 … 3, the mode of operation " Pump control 4" is adjusted with the option " Sequenced operation". The relay switching points are configured as follows: VEGAMET 341 • 4 … 20 mA...
Page 38
HiHi level is exceeded and the dry weather pump is switched off. The large pump then remains in operation until the switch-off point is reached. If the level rises again, the dry weather pump switches back on first. There is also the possibility of using multiple large pumps in alternat- ing mode. The algorithm for the switching function is then determined by the pump control mode. VEGAMET 341 • 4 … 20 mA...
Page 39
Since in this case all pumps operate alternately in the same area, their switch-on and switch-off points must be the same. In addition, the mode " Alternating pump operation" must be active. VEGAMET 341 • 4 … 20 mA...
Rectangular flume (ISO 4359) • Trapezoidal flume (ISO 4359) • U-shaped flume (ISO 4359) • • Triangular overfall thin-walled (ISO 1438) Rectangular flume thin-walled (ISO 1438) • • Rectangular weir broad crown (ISO 3846) Flow formula If the flow formula of your flume is known, you should select this op- tion, as the accuracy of the flow measurement is highest here. • Flow formula: Q = k x h VEGAMET 341 • 4 … 20 mA...
Page 41
3 ... 4 h 90° 90° Fig. 19: Flow measurement with rectangular flume: h = max. filling of the max. rectangular flume Overfall orifice (side view) Upstream water Tailwater Overfall orifice (view from tailwater) VEGAMET 341 • 4 … 20 mA...
Page 42
The measuring range suitable for the application should be set di- rectly in the sensor to achieve the maximum accuracy. This measuring range must now be stored once again in the assistant together with the sensor type and measuring unit. Define application Select the appropriate linearization and flume type. A list of available flumes can be found in the introduction to this application. VEGAMET 341 • 4 … 20 mA...
Page 43
DTM/VEGA Tools app • via a digital input (e.g. via button) • time controlled (daily at any time) Configure measured value indication In the last step you can configure which and how many measured values are to be shown on the display. In addition, you can define the base of the display value, the display format and the optional bar graph. VEGAMET 341 • 4 … 20 mA...
• Evaluation of fault messages • Checking the input/output signal A smartphone/tablet with the VEGA Tools app or a PC/notebook with the software PACTware and the suitable DTM offer you further com- prehensive diagnostic possibilities. In many cases, the causes can be determined in this way and the faults eliminated.
Page 45
No operable software Software update failed Switch the instrument off and on F037 RAM defective Carry out a reset Send instrument for repair Switch the instrument off and on F040 Hardware error Carry out a reset General hard- Send instrument for repair ware error VEGAMET 341 • 4 … 20 mA...
Function check Rectification Error code Cause C029 Simulation active Finish simulation Simulation 11.4 Software update An update of the device software is possible via the Bluetooth inter- face. The following components are required: VEGAMET 341 • 4 … 20 mA...
• Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Ask the agency serving you to get the address for the return ship- ment. You can find the agency on our homepage. VEGAMET 341 • 4 … 20 mA...
12.2 Disposal The device is made of recyclable materials. For this reason, it should be disposed of by a specialist recycling company. Observe the ap- plicable national regulations. VEGAMET 341 • 4 … 20 mA...
That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observ- ing the environmental instructions in chapters " Packaging, transport and storage", " Disposal" of these operating instructions. VEGAMET 341 • 4 … 20 mA...
Adjustment range 4 … 20 mA sensor Ʋ Empty adjustment 2.4 … 21.6 mA Ʋ Full adjustment 2.4 … 21.6 mA Temperature error relating to 20 mA 0.008 %/K Relay output 3 x operating relay, one can be configured as fail safe Quantity relay VEGAMET 341 • 4 … 20 mA...
Page 51
If inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be permanently damaged. The contact is then no longer suitable for switching low-level signal circuits. Depending on the local conditions VEGAMET 341 • 4 … 20 mA...
Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.