Cleaning The Condensate Siphon; Cleaning The Filter In The Cold Water Inlet; Cleaning The Heating Filter - Glow-worm EASICOM 3 28c Installation And Maintenance Instructions Manual

Hide thumbs Also See for EASICOM 3 28c:
Table of Contents

Advertisement

7.
Using water to clean the condensate tray (1).
The water runs out into the condensate siphon.

11.11 Cleaning the condensate siphon

C
1.
Unclip the lower section of the siphon (1) from the up-
per section of the siphon (2).
2.
Remove the float (3).
3.
Flush out the float and lower section of the siphon with
water.
4.
Fill the lower section of the siphon with water up to 10
mm below the upper edge of the condensate drain pipe-
work.
5.
Reinsert the float (3).
Note
Check whether the float is present in the
condensate siphon.
6.
Clip the lower section of the siphon (1) into the upper
section of the siphon (2).
0020239562_02 EASICOM 3 Installation and maintenance instructions
1
2
B
A
3
1
Inspection and maintenance 11

11.12 Cleaning the filter in the cold water inlet

1.
Close the main cold water supply line.
2.
Drain the product on the hot water side.
3.
Remove the connection piece from the connection for
the product's cold water supply.
4.
Clean the filter in the cold water inlet without removing
it.

11.13 Cleaning the heating filter

2
1
1.
Drain the product. (→ Page 26)
2.
Remove the temperature sensor (1).
3.
Remove the upper clip (2).
4
5
4.
Remove the lower clip (3).
5.
Remove the flow pipe (4).
6.
Remove the heating filter (5) and clean it.
7.
Refit the components in the reverse order.
3
25

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EASICOM 3 28c and is the answer not in the manual?

Questions and answers

John Large
January 19, 2025

can you a supupumpmantery

This manual is also suitable for:

Easicom 3 24c

Table of Contents

Save PDF