SCU100 INSITE PRO M COMPACT USER MANUAL

10.4.Alarms

This page allows to set alarms. If an alarm occurs, it is shown in the "Analytics – Alarms log" section. An alarm
can occur after exceeding the selected threshold values (cross-up), after measuring values lower than the
selected threshold values (cross-down) for a determined period (time delay) or if a certain status changes
(status change). The email report is sent after 1 minute from the first event occurance and consists of all
alarms that occured in this period. The next report can only be sent after at least 30 minutes since the first
alarm occurance and only in case event conditions are still ongoing.
If a SNMP trap is set up, a notification of the event will be sent.
When adding or editing an alarm, please set the following:
Name
Category
Device
Alert Type
Measure
Threshold
Time delay
Email notification
SNMP trap
Set the name of the alarm
Select the type of the device (Control unit, Meters,
Current sensors, I/O Modules)
Select the devices already defined in "Configuration –
Devices" according to the Category selected
Type of alarm: "No event", "Cross-up", "Cross-down".
"Status change" only in case of I/O Modules devices
Set the specific measure to monitor according to the
device selected
Threshold of selected measure
Define for how long the event criteria should be fulfilled
in order to consider the occurrence as an event
If the box is selected, an email will be sent when an alarm
occurs. The email address has to be defined in "Settings
– Email, FTP".
If the box is selected, notification of alarm will be sent
via SNMP trap. SNMP trap settings have to be defined in
"Settings – Communication / SNMP trap"