Rtd Input Module Characteristics; Temperature Conversion Characteristics; Conversion Speed; Accuracy - LG MASTER-K G4F-TC2A User Manual

Programmable logic controller
Hide thumbs Also See for MASTER-K G4F-TC2A:
Table of Contents

Advertisement

Chapter 2. SPECIFICATIONS

2.4 RTD Input Module Characteristics

2.4.1 Temperature Conversion Characteristics

The RTD input module, as shown in the Fig. 2.1, linearlizes the non-linear characteristic resistance
input of the RTD.
[Fig. 2.1] Temperature conversion characteristics( Pt100)

2.4.2 Conversion speed

The conversion speed of the RTD input module is 50 ms per channel and its processing is
processed sequentially, that is, one channel is processed and then another channel is
processed.
Processing time = 50 ms the number of the used channels
Example) When three channels are used
2.4.3

Accuracy

The accuracy of RTD input module is within ±0.5 % of all of the measurable temperature range.
Example) When the RTD Pt100 is used, the conversion values of –100°C and 400°C are as
below.
- Measurable temperature full range : 800°C (-200.0°C to 600.0°C)
- Accuracy : 800 (±0.5%) = 800 (±0.005) = ±4°C
- Temperature conversion range : - 104 °C to – 96 °C when –100°C
Resistance
temperature
detection value
Processing time = 50 ms 3 = 150 ms
2 - 5
396°C to 404°C when 400°C

Advertisement

Table of Contents
loading

This manual is also suitable for:

Glofa g3f-rd3a

Table of Contents