(b) Regulations regarding immunity
Specification
EN61000-4-2
Electrostatic
discharge
immunity
EN61000-4-3
Radiated, radio-
frequency,
electromagnetic
field immunity
EN61000-4-4
Electrical fast
transient/burst
immunity
EN61000-4-5
Surge
immunity
EN61131-2:
2007
EN61000-4-6
Immunity to
conducted
disturbances,
induced by
radio-frequency
fields
EN61000-4-8
Power-
frequency
magnetic field
immunity
EN61000-4-11
Voltage dips and
interruption
immunity
*1 Programmable controllers are open-type devices (devices designed to be housed inside
other equipment) and must be installed inside a conductive control panel. The tests were
conducted with the programmable controller installed in a control panel.
*2 The accuracy of an analog-digital converter module may temporary vary within ±10%.
Test item
Test details
Immunity test in
which electrostatic is
applied to the cabinet
*1
of the equipment.
Immunity test in
which electric fields
are irradiated to the
product.
*1
Immunity test in
which burst noise is
applied to the power
*1
line and signal line.
Immunity test in
which lightning surge
is applied to the
*1
power line and signal
line.
Immunity test in
which high frequency
noise is applied to the
power line and signal
line
*1
Immunity test in
which the product is
installed in inductive
magnetic field
*1
Immunity test in
which power supply
voltage is
momentarily
*1
interrupted
• 8kV Air discharge
• 4kV Contact discharge
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
• AC/DC main power, I/O power,
AC I/O (unshielded): 2kV
• DC I/O, analog, communication
: 1kV
• AC power line, AC I/O power,
AC I/O (unshielded)
: 2kV CM, 1kV DM
• DC power line, DC I/O power
: 0.5kV CM, DM
• DC I/O, AC I/O (shielded),
analog
0.15M-80MHz, 80% AM modulation
@1kHz, 10Vrms
50Hz/60Hz, 30A/m
• Apply at 0%, 0.5 cycles and zero-
cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
42
Standard value
*2
, communication: 1kV CM