Surface mounted installation

Surface-mounting the product on the ceiling using
suspension bracket SYST MD-ADRIATIC.
1. Carefully measure where the bracket is to be placed so that
all the brackets are in a perfectly straight line in relation to
each other according to the c-c table. The bracket's distance
to the edge of the short side may not exceed 250 mm, in
order for the safety cord to be able to be anchored.
2. Install the suspension bracket SYST MD-ADRIATIC in the
ceiling. Use two brackets per product for lengths 1.2 and
1.8. For lengths 2.4 and 3.0, use three brackets. Anchor the
safety cord under the suspension bracket when installing the
bracket. Use a suitable screw for the ceiling in question.
3. When all the brackets have been screwed into place with
four screws each, fold out the moving sections at either end
of the bracket to the out position.
4. Anchor the enclosed safety cord in the bracket and in the
corner of the product.
5. Then move the product straight up against the bracket.
6. Lock the product in the bracket by pressing the folded out
sections on the ends of the bracket in towards the product
on both sides.
7. Repeat this procedure for all the brackets.
Y= < 250
1
Y= < 250
X=280
X=280
23/03/2023
Installation
The c-c dimensions are the same for WISE Adriatic with
both design module Prisma and design module Ellips. The
examples below show Prisma.
Surface mounted installation
Number of
Unit
brackets
(m)
pcs.
1.2
2
1.8
2
2.4
3
3.0
3
* Max. distance from the end of the product.
c-c 23,5
3
4
Swegon reserves the right to alter specifications.
WISE Adriatic
c-c (mm)
Max. (mm) *
X - Short side
Y - Long side
280
250
280
250
280
250
280
250
c-c 23,5
c-c 280
2
5