Connecting

6.1

Safety when connecting up

Safety notices
When connecting up the device, keep to the safety notices listed below.
Power supply
The device is designed for operation with a directly connectable safety extra low voltage (SELV)
from a limited power source (LPS).
The power supply therefore needs to meet at least one of the following conditions:
• Only safety extra low voltage (SELV) with limited power source (LPS) complying with IEC
• The power supply unit for the device must meet NEC Class 2 according to the National
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
Note
A power source that supplies safety extra low voltage combined with a following NEC Class 2
power limiter also meets the requirements according to IEC 60950‑1 / EN 60950‑1 / VDE 0805‑1
or NEC Class 2. A suitable power limiter is for example the redundancy module SITOP PSE202U
NEC Class 2 (article number 6EP1962-2BA00).
Note
Safety extra-low voltage
The supply of the devices by PELV (Protective Extra Low Voltage) according to DIN VDE 0100-410
or IEC 60364-4-41 is permitted when the generated nominal voltage does not exceed the
voltage limits 25 VAC or 60 VDC.
SCALANCE X-300M
Compact Operating Instructions, 05/2023, A5E02630801-14
WARNING
60950‑1 / EN 60950‑1 / VDE 0805‑1 or IEC 62368-1 / EN 62368-1 / VDE 62368-1 may be
connected to the power supply terminals.
Electrical Code (r) (ANSI / NFPA 70).