1/4 turn actuators

Advertisement

Quick Links

RedMax
¼ turn actuators – size M
Electrical, explosion proof rotary actuators
On-off / 3-pos. control mode, 24...240 VAC/DC, 95° angle of rotation incl. 5° pretension
50 / 75 – 100 – 150 Nm without and 30 – 50 – 60 Nm with safety operation (spring return)
ATEX tested in acc. with directive 2014/34/ EU for zone 2, 22
Compact. Easy installation. Universal. Cost effective. Safe.
Type
Torque
RedMax- 50.75
50 / 75 Nm
RedMax- 100
100 Nm
RedMax- 150
150 Nm
RedMax- 30 - F
30 Nm
RedMax- 50 - F
50 Nm
RedMax- 60 - F
60 Nm
RedMax- ... - S /SF Types as above with 2 integrated, potential free auxiliary switches, 5° and 85° angle of rotation
RedMax- ... - CTM Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
RedMax- ... - VAM Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)
Product views and applications
Safety damper
Ball valve
Description
The RedMax actuators are a revolution for safety, control and shut-off
dampers, ball valves, throttle valves and other motorized applications for
HVAC systems in chemical, pharmaceutical, industrial and offshore/onshore
plants, for use in Ex-areas zone 2 (gas) and zone 22 (dust).
Highest protection class (ATEX) and IP67 protection, small dimensions,
only 9,5 kg weight, universal functions and technical data, an integrated
heater and an optional stainless steel housing guarantee safe operation
even under difficult environmental conditions. High quality brushless
motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times and torques are selectable
or adjustable on site. The integrated universal power supply is self
adaptable to input voltages in the range of 24...240 VAC/DC. The actuators
are 100 % overload protected.
...Max-...F actuators are equipped with spring return fail safe function.
Standard shaft connection is a double square direct coupling with
16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
Supply
Motor running time
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s /90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s /90°
24...240 VAC/DC
40 / 60 / 90 / 120
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
24...240 VAC/DC
40 / 60 / 90 / 120
Throttle valve
Highlights
► For all types of gases, mists, vapours and dusts in zones 2 and 22
► Universal supply unit from 24...240 VAC/DC
►Different motor running times 40– 60 –90 –120 –150 s/ 90°, adjustable on site
► Spring return running time ~ 20 s/ 90°
► On-off and 3-pos. control with or without spring return function
► 30 – 50 –60–75– 100– 150 Nm actuators in the same housing size
► 100 % overload protected
► Compact design and small dimension (L × W × H ~ 288 × 149 × 116 mm)
► Direct coupling to the damper shaft with double square connection 16 × 16 mm
► 95° angle of rotation inclusive 5° pretension
► Robust aluminium housing (optional with seawater resistant coating)
or in stainless steel
► IP67 protection
► Simple manual override included + preparation for comfortable manual override
► Gear made of stainless steel and sinter metal
► Weight only ~ 9,5 kg
► Integrated heater for ambient temperatures down to −40 °C
► Integrated safety temperature sensor
► Integrated equipment for manual adjustment (push button, lamp, switch)
► Preparation for adaptable and adjustable auxiliary switches type ...Switch
► Wide range of accessories
www.schischek.com
E X P L O S I O N P R O O F
Spring return
Control mode
On-off, 3-pos.
On-off, 3-pos.
s/90°
On-off, 3-pos.
~ 20 s/90°
On-off, 3-pos.
~ 20 s/90°
On-off, 3-pos.
s /90°
~ 20 s/90°
On-off, 3-pos.
RedMax - ...
RedMax - ... - F
RedMax - ... - S
RedMax - ... - SF
RedMax - ... - CTM
RedMax - ... - VAM
Subject to change!
Feedback
Wiring diagram
SB 1.0
SB 1.0
SB 1.0
SB 2.2 / 2.3
SB 2.2 /2.3
SB 2.2 / 2.3
2 × aux. switches
SB 3.0
RedMax-M-3P_en
V04 –
14-Jan-2019
1 / 4

Advertisement

Table of Contents
loading

Summary of Contents for Schischek RedMax F Series

  • Page 1 ► Preparation for adaptable and adjustable auxiliary switches type ...Switch ► Wide range of accessories RedMax-M-3P_en V04 – 14-Jan-2019 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 1 / 4...
  • Page 2: Special Option

    RedMax-...-S3 Ambient temperature up to +60 °C (T4), 110...240 VAC/ DC, 25 % ED RedMax-M-3P_en V04 – 14-Jan-2019 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 2 / 4...
  • Page 3: Electrical Connection

    Wiring of the integrated, potential free application see diagrams above auxiliary switches RedMax-M-3P_en V04 – 14-Jan-2019 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 3 / 4...
  • Page 4 ...Max-... and ...Max-...-F They are connected by cable. RedBox- Y/S for ...Max-...-S and ...-SF RedMax-M-3P_en V04 – 14-Jan-2019 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 4 / 4...
  • Page 5 Otherwise the fuse could respond and switch off the actuator irreversibly. info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 1 / 6...
  • Page 6 For square damper shafts 12 × 12 mm or 14 × 14 mm reducing bushes are available as optional accessories. info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 2 / 6...
  • Page 7 Mounting to a ball valve Mounting to a butterfly valve 4 × 4 × info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 3 / 6...
  • Page 8 B) Mount ...Switch and fix it with screws ...Max with mounted ...Switch 4 × info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 4 / 6...
  • Page 9 24 V power supply with wire diameter 1.5 mm² = cable length 126 m electrolytic copper with a coefficient of 56 m /Ωmm²) info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 5 / 6...
  • Page 10 ● Cable to long, voltage drop in the supply line to large ● Increase line cross section or power supply info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 6 / 6...
  • Page 11: Sales Contact

    SALES CONTACT www.airmax-hvac.com 080-614-4944, 063-268-8080 @airmax (Line Official) windcontrol.info@gmail.com Address เลขที 56/392 หมู ่ ท ี 12 ตํ า บลศี ร ษะจรเข้ น ้ อ ย อํ า เภอบางเสาธง จั ง หวั ด สมุ ท รปราการ 10540...