ActronAir ESP ULTIMA SYSTEM Installation & Commissioning Manual

ActronAir ESP ULTIMA SYSTEM Installation & Commissioning Manual

With lm series wall controllers

Advertisement

Quick Links

INSTALLATION & COMMISSIONING GUIDE
with LM Series Wall Controllers
This manual is a controlled document which contains confi dential and proprietary information.
Distribution, modifi cation, copying and/or reproduction are prohibited without written consent from ActronAir.
®
Copyright © 2013 Actron Engineering Pty. Ltd. All rights reserved.
ULTIMA SYSTEM
MON TUE WED THU FRI SAT SUN
AM
PM
LOW
SET TEMP
SET TEMP
TIME CLOCK
ON
ON
OFF
TIMER
EVENT
OFF
o
o
C
C
1
2
INSIDE
SET
RUN
FILTER
MED
HIGH
AUTO
HEAT
COOL
CONT
AUTO
AUTO
FAN
HEAT / COOL
HEAT / COOL
PROGRAM
TIMER
SELECT
EXIT
REPEAT /
REPEAT /

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ESP ULTIMA SYSTEM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ActronAir ESP ULTIMA SYSTEM

  • Page 1 REPEAT / REPEAT / Copyright © 2013 Actron Engineering Pty. Ltd. All rights reserved. This manual is a controlled document which contains confi dential and proprietary information. Distribution, modifi cation, copying and/or reproduction are prohibited without written consent from ActronAir.
  • Page 2: Table Of Contents

    © ActronAir Ultima System...
  • Page 3: Parts Specifications

    PARTS SPECIFICATIONS STANDARD PARTS SUPPLIED WITH ULTIMA FAN COIL ULTIMA MODULE Part Number : 8Z-VAV Voltage : 240V & 24 VAC Dimensions - mm : 230 x 92 x 55 (W x H x D) Connections : RJ45 Socket LM - SERIES MASTER WALL CONTROLLER MON TUE WED THU FRI SAT SUN TIME CLOCK Part Number :...
  • Page 4 RJ45 4070-018 12 metres RJ45 3-WAY CABLE JOINER (Sold Separately) Part Number : 4070-012 Connector Type : RJ45 Cable Length : 175mm (Included) 2-WAY CABLE JOINER (Sold Separately) Part Number : 2045-121 Connector Type : RJ45 © ActronAir Ultima System...
  • Page 5: Installation

    INSTALLATION Installing the Master Controller (LM7-D) WALL CONTROLLER BACK COVER WALL CONTROLLER INSERT SCREWDRIVER AND TWIST SLOTS SCREW DRIVER PLASTERBOARD MOUNTING BRACKET 1. Remove front cover, as shown. 2. Mount back cover to the wall. • Use large enough fl at blade screwdriver to fi t into the •...
  • Page 6: Installing The Zone Controller (Lm-Zc)

    SPONGE Feed the zone cable through the wall opening, taking care not to damage the barb. Protect the RJ45 connector barb by using tape. Fit anti-draft sponge to stop wall drafts infl uencing the temperature sensor. © ActronAir Ultima System...
  • Page 7 Z O N E C O N T R O L ROOM TEMP COVER TEMP MODE ON/OFF PLATE TEMPERATURE SENSOR NOTE: When fi tting the cover plate, ActronAir logo should be shown at the bottom (as shown) to avoid damaging the temperature sensor. Copyright © 2013 Actron Engineering Pty. Ltd.
  • Page 8: Installing Remote Sensor (Lm-Zs)

    Insert the RJ45 connector to the Zone Sensor socket, making sure a full connection. The barb will click into place when the RJ45 plug sits fully unto the zone sensor. NOTE: It is recommended to use Wall Mates to secure mounting screws tightly against the wall. © ActronAir Ultima System...
  • Page 9 Actron Controls LOGO SHOWN RIGHT WAY UP SENSOR COVER PLATE NOTE: When fi tting the cover plate, ensure that ActronAir logo is shown right way up. (See illustration for correct installation as shown above). Copyright © 2013 Actron Engineering Pty. Ltd.
  • Page 10: Connection Diagram

    STUD IMPORTANT NOTE: It is necessary to use ActronAir RJ45 3-Way connector when averaging remote sensors is required. Communication cable between 8-zone Ultima module and RJ45 3-Way cable joiner must not exceed 175mm (RJ45 3-Way joiner is supplied with 175mm cable).
  • Page 11: Controller And Temperature Sensor Wiring

    CONTROLLER AND TEMPERATURE SENSOR WIRING A. ONBOARD SENSOR ONLY DATA CABLE FROM ULTIMA MODULE 8Z-VAV DO NOT REMOVE LINK ZONE ZONE ZONE ZONE ZONE ZONE ZONE ZONE ZONE ZONE CONTROLLER LM-ZC MOTOR AMIB DATA LINK DATA CABLE FROM B. ONE ZONE SENSOR ONLY ULTIMA MODULE 8Z-VAV ZONE...
  • Page 12: System Wiring Diagram

    ZONE SENSOR FAMILY KITCHEN RUMPUS DINING LM-ZS MASTER BED MASTER BED BEDROOM 1 BEDROOM 1 BEDROOM 2 BEDROOM 2 BEDROOM 3 BEDROOM 3 ZONE MOTOR LINK ZONE CONTROLLER C C C C CONT LM-ZC OUTDOOR UNIT © ActronAir Ultima System...
  • Page 13: Maximum Cable Lengths

    50 m Long runs beside MAIN cable and TV antenna cables should be avoided where possible. ActronAir CAT5E zone cables must be used:- 4070-013 (7m), 4070-018 (12m), 4070-014 (20m). Always run the minimum possible length of zone cable. 2-Way Cable Joiner (2045-121) also available. Same max. cable length apply.
  • Page 14 Trace wire connects to SCN/COM terminal at Outdoor PCB and to SCN on Indoor PCB. Do not connect at Wall Controllers. NOTE: DIAGRAM SHOWN ABOVE IS A GENERAL PRESENTATION ONLY. REFER TO INDIVIDUAL UNIT WIRING DIAGRAM FOR COMPLETE WIRING CONNECTION DETAILS. © ActronAir Ultima System...
  • Page 15: Master Controller

    OPERATION MASTER WALL CONTROLLER & SECONDARY WALL CONTROLLER COOL COOL CONT AUTO AUTO AUTO AUTO HEAT / COOL HEAT / COOL HEAT / COOL HEAT / COOL TIMER PROGRAM TIMER SELECT SET TEMP SET TEMP SELECT TEMP DISPLAY EXIT REPEAT / REPEAT / MASTER WALL CONTROLLER SECONDARY WALL CONTROLLER...
  • Page 16: Zone Controller Identifi Cation

    TEMP MODE ON/OFF ROOM TEMPERATURE BUTTON When pressed displays the actual room temperature reading and room temperature LED fl ashes. MODE ON/OFF BUTTON Press to turn ON or OFF the zone. (FACTORY DEFAULT SETTING) © ActronAir Ultima System...
  • Page 17: System Start Up

    OPERATION SYSTEM START UP During initial system start up, zone control will boot up and show zone number. During this period the LED display will initially show a horizontal bar moving back and forth. Once detected, its zone number will be displayed for several seconds before normal display (temperature set point) will be shown.
  • Page 18 REPEAT / REPEAT / EXIT To turn OFF, press the zone button. The light in the zone button will turn OFF. FAMILY KITCHEN RUMPUS DINING MASTER BED BEDROOM 1 BEDROOM 2 BEDROOM 3 © ActronAir Ultima System...
  • Page 19: Turning Zone On And Off

    OPERATION TURNING ZONE Zone activation or de-activation via Zone Controller. ZONE CONTROL: Press the zone button to be activated. The light in the zone ZONE COOL HEAT button will turn ON indicating zone AUTO is ON. Z O N E C O N T R O L Turn A/C ON at master wall controller.
  • Page 20: Zone Controller Modes Of Operation

    TIMER ON operation (master wall controller). This will allow the user to change the set point temperature (even when zone control is off) to bring up the desired temperature when the unit is activated via TIMER ON function. © ActronAir Ultima System...
  • Page 21 OPERATION ESP AUTO MODE The system will allow the zone controller to automatically control the ZONE COOL position of zone damper blade. The opening angle of damper blade will ESP AUTO depend on the room temperature and set point temperature requirement. Pressing temperature UP button will increase room temperature.
  • Page 22: Display Room Temperature

    During this period the “INSIDE,” “ C,” and “ ” PROGRAM TIMER indicators will be fl ashing. SET TEMP SET TEMP SELECT REPEAT / REPEAT / EXIT FAMILY KITCHEN RUMPUS DINING MASTER BED BEDROOM 1 BEDROOM 2 BEDROOM 3 © ActronAir Ultima System...
  • Page 23: View Individual Room Temperature

    OPERATION TO VIEW TEMPERATURE IN EACH INDIVIDUAL ZONES WITH MASTER WALL CONTROL 1. Press SELECT Up or Down button. 2. While the “INSIDE,” “ C,” and “ ” indicators are fl ashing, press the zone area to be checked. At this time “INSIDE,”...
  • Page 24: Mounting Dimensions

    MOUNTING DIMENSIONS ZONE CONTROL (LM-ZC) * Drawn not to scale. ZONE SENSOR (LM-ZS) 20.5 mm MAXIMUM CUT-OUT SIZE 18mm x 20mm 18 mm 41 mm © ActronAir Ultima System...
  • Page 25: Frequently Asked Questions

    FREQUENTLY ASKED QUESTIONS Q. Does the backlight on the individual zone control effect brightness of the room at night? A. The display backlight turns off at approximately 30 seconds after any button is pressed. Q. Does the LM7-D come standard with all R410a ESP Ultima units? A.
  • Page 26 Q. Does the Ultima system use a different zone barrel to the standard ON/OFF type 24volt Actron Air barrels? A. No, they are the same barrels. ActronAir designed these zone motors with the intension to communicate with the Ultima system.
  • Page 27 FREQUENTLY ASKED QUESTIONS A. No need, when the system is initially powered up the Ultima system will automatically acquire the utilized zones. Because each zone has its sensor there’s no need to assign sensor’s either. Q. If I am not in ESP mode on the master will my zone still modulate the airfl ow? A.
  • Page 28 For further information visit, www.actronair.com.au For technical assistance or service call enquiries call: 1800 119 229 Actron Engineering Pty. Ltd. Printed in Australia ABN 34 002 767 240 Part Number: 0500-123 Version: 4.0 130625 HEAD OFFICE NORWEST BUSINESS PARK SYDNEY AUSTRALIA...