2. Hardware
2.1 Specifications
Module
Communication
Ports
Data Format
Baud Rate
Protocol
Software
Function
Node Addresses
LED Display
Status
EMS Protection
ESD (IEC 61000-4-2)
EFT (IEC61000-4-4)
SURGE(IEC 61000-4-5)
Power
Reverse Polarity
Protection
Input Voltage Range
Consumption
Mechanical
Dimensions (W x L x H)
Installation
Environment
Operating Temperature
Storage Temperature
Humidity
LC-101H
N,8,1/O,8,1/E,8,1/N,8,2
Hardware Configuration: Fixed 9600 bps
Software Configuration: 1200 to 115200 bps
Modbus RTU / DCON
Local and Remote Direct Control Relay ON/OFF and
Remote Status Monitoring
32 to 63 for hardware configuration
1 LED as Power Indicator
±4 kV Contact for each Terminal
1.9 W Max.
72 mm x 95 mm x 57 mm
10 to 95% RH, Non-condensing
LC-101H/LC-102H User Manual
- 6 -
1 x RS-485
±4 kV for Power
±2 kV for Power
Yes
10 ~ 30 VDC
2.8 W Max.
DIN-Rail
-25 to +75°C
-30 to +80°C
LC-102H