Connecting the temperature sensor, float sensor and lay-off bu�on of the beeper
3.
Connecting the visual and acoustic alarms and the emergency valve
4.
Selec�ng the supply voltage and the maximum current load
5.
Supply voltage 230 VAC
The highest current load of the controller is 430 mA. This current serves to power the connected transmitters and the visual
and acous�c alarms, which are connected to the terminal blocks „LIGHT_SIG" and „SOUND_SIG".
Example: There are 4 transmitters connected to the detector with a consump�on of 60 mA each, which leaves us with 190 mA (I=430-4x60)
to supply the visual and acous�c alarms.
Supply voltage 24 VDC
The consumption of the controller's electronics is 200 mA. The maximum current on terminal blocks „+24 V IN/OUT" is 8 A.
The maximum current load on each output of the terminal blocks „LIGHT_SIG" and „SOUND_SIG" is 4 A.
Example: We have connected 4 transmi�ers with a consump�on of 60 mA. The controller has a consump�on of 200 mA. We have 7.46 A
(I=8000-300-4x60) for powering op�cal and sound signaling.
Informa�on on the consump�on of each transmitter and component of the visual and acous�c alarms is provided in the
respective manuals.
Never connect the supply voltage 24 V and 230 V simultaneously.