Add-On Modules And Accessories; A�Achments; Table Of Error Codes - DEGA UKA III Instruction Manual

Table of Contents

Advertisement

Add-on modules and accessories

Product code
10200002
DEGA UKA III Power
10200003
DEGA UKA III Relay Module
10200005
DEGA UKA III Memory Modul
10300005
UPS External Battery Backup
10300013
Cable Glades PG11 (10pcs)
10300014
External power supply 30 W, 24 VDC
10300015
External power supply 60 W, 24 VDC
10300016
External power supply 120 W, 24 VDC
10300017
External power supply 240 W, 24 VDC
10300018
Intrinsic safety Zener barrier 28 V, 300 Ohm, 93 mA
10300019
Moun�ng box for Zener barriers
10300021
DEGA Configuration&Calibra�on software
Attachments

1. Table of error codes

Displayed on auxiliary
segments
„SENSOR E"
„ NO SENS"
„UNK SENS"
„ELCHEM E"
„SENS CRC"
„LMP9 ERR"
„SEN MISM"
„ELFAILED"
„ HEATING"
„EE25 ERR"
„FLASHCRC"
„EEPR CRC"
„INFRA ER"
„ CALIB18"
„COMM ERR"
Name
Cause
Interrupted current loop
or faulty transmitter
Sensor is not present
(EEPROM of the sensor is
not communica�ng)
Unknown sensor type
Type 2 sensor ID not
found in the se�ngs
table LMP91000
CRC does not match the
sensor EEPROM
LMP91000 is not
responding
The set sensor ID does
not match with the
connected sensor.
EL sensor test error
Transmitter is in
prehea�ng mode
Error in reading the
internal FLASH
Error in reading the
internal FLASH
Error in reading the
internal FLASH
Infrared sensor error
The device exceeded the
maximum calibration
interval by 50 %
The transmitter isn't
responding
Internal Power Supply 230 V AC/15VA
Internal 3-relays, 250 V/10 A
Internal memory with battery
Ba�ery Backup 12 Ah/24 Ah
with external moun�ng box
with external moun�ng box
with external moun�ng box
with external moun�ng box
IP 54 (30 x 22 x 12 cm) with DIN rail
Configura�on software DEGA Config with USB Cabel
Solu�on
Check the transmitter connection, otherwise
contact the manufacturer.
Disconnect and reconnect the sensor, then
restart the sensor by disconnec�ng and
reconnec�ng the power.
Contact the manufacturer.
Contact the manufacturer - FW update
required.
Sensor error - contact the manufacturer.
Sensor error - contact the manufacturer.
Checking the configura�on of the sensor
required.
Sensor error, only informative, subsides by
itself.
Wait a few minutes, the transmitter will
automa�cally enter measurement mode.
Restart the transmitter. If the error persists,
contact the manufacturer.
Restart the transmitter. If the error persists,
contact the manufacturer.
Restart the transmitter. If the error persists,
contact the manufacturer.
Replace the sensor.
Calibra�on is necessary.
Check the connection between the controller
and the transmitter