Piping Diagram
7-3 Functions (cont.)
7-3-2 Control (cont.)
7-3-2-6 Indoor unit control (cont.)
Temperature Compensation
▪ Purpose
Compensate for variances in temperature affecting people differently in the room. Wind chill is caused by indoor tempera-
ture stratification when using the internal temp sensors on indoor units instead of using external temp sensors in the room.
▪ Concept
If measuring the indoor temperature using the internal temp sensors on indoor units in heating mode, the temperature is
controlled under the assumption that the actual indoor temperature is lower than the temperature inside the indoor units
and the temperature difference is equivalent to the compensation temperature.
▪ Control specifications in detail
∙ Factory default (product option code SEG6)
- 4way type : △ T* = 5 K
- others : △ T* = 2 K
∙ Installation setting( installation option code SEG21)
SEG21 Setting
0
1
2
* △ T : Heating compensation temperature
∙ In case of using external room temp. sensor
( Installation option SEG4 = 1 ) : △ T = 0
▪ Notes
- Order of priority : Use of external temp sensor > Install offset > Basic option.
Samsung Electronics
△ T*
Factory default
2 K
5 K