Download Print this page
DeDietrich VIVADENS MCR Technical Information

DeDietrich VIVADENS MCR Technical Information

Wall-hung gas condensing boilers

Advertisement

Quick Links

Technical Sales Documentation
Department
EN
P5253 JS F 67580 Mertzwiller
1. Description of the modifications
A thermal fuse has been added in the upper part of the heat exchanger front plate. The thermal fuse is connected in
series with the overheating safety thermostat of the heat exchanger.
The thermal fuse shuts down the boiler if the temperature reaches 128 °C and the error E13 appears.
Application date in series: 22 september 2014.
As of serial number 1426209919550.
Thermal fuse
TB
During the annual maintenance, check the burner plate insulation and imperatively replace the gaskets. In spare parts,
the burner plate insulation is systematically delivered with a thermal fuse, which is to be mounted on the heat exchanger
front plate.
The thermal fuse is also delivered with the maintenance kit available from the Spare Part Centre (see kits hereafter).
see the leaflet delivered with the kit : Reference 7619580 (Click on the reference to open the link).
Re20140930
N° IT2621
New version
1 / 3
Wall-hung gas condensing boilers
VIVADENS MCR, MCR-P, MCR BIC
Previous version
G000790
T
Technical information
Heading No 5
MCX
Product evolution
26/11/2014
IT2621

Advertisement

loading

Summary of Contents for DeDietrich VIVADENS MCR

  • Page 1 Technical Sales Documentation Technical information Department Heading No 5 Wall-hung gas condensing boilers VIVADENS MCR, MCR-P, MCR BIC Product evolution P5253 JS F 67580 Mertzwiller N° IT2621 26/11/2014 1. Description of the modifications A thermal fuse has been added in the upper part of the heat exchanger front plate. The thermal fuse is connected in series with the overheating safety thermostat of the heat exchanger.
  • Page 2 2. Spare parts Kits available in the Spare part Centre: Reference Description Heat exchanger front plate insulation disk 7619579 (Insulation + Thermal fuse) 7619082 Maintenance kit (see picture below) For more detailed information, see the leaflet delivered with the kit : Reference 7619580 (Click on the reference to open the link).
  • Page 3 4. Service operations The front plate insulation disk is an important part to ensure safe operation of the boiler and must therefore be in good condition. A damaged front plate insulation disk can lead to leakage on the flue gas side. Check the front plate insulation disk for cracks, damage, moisture, ageing or distortion.

This manual is also suitable for:

Vivadens mcr-pVivadens mcr bic