5.2

Configuring the JUMO IO device

Using the JUMO variTRON 500 by way of example, this chapter explains how to integrate and configure
a PROFINET IO device in CODESYS® using the setup program (JUMO smartWARE Setup variTRON)
so that it can be found by an IO controller. This can then assign the IO device a device name and an IP
address.
First, configure the network settings of the JUMO variTRON 500 using the device display:
chapter 5.2.1 "Network settings", Page 17
Then use the setup program to create and open a CODESYS® project:
chapter 5.2.2 "Configuration in CODESYS® (using the setup program)", Page 18
The configuration process for the PROFINET IO device is described in steps 1 to 8. Once the configu-
ration work is complete, close the CODESYS® project in the setup program and apply the changes. You
can then load the application into the JUMO variTRON 500.
The
CODESYS®
JUMO variTRON 500. Direct transfers from CODESYS® are described in steps 12 to 14.
NOTE!
If possible, do not use the LAN1 interface for the configuration work as LAN1 is used for PROFINET.
Otherwise an error message will occur when starting up the system for the first time.
chapter 6.2 "Error message in the setup program", Page 35
Use either a free LAN port (e.g. LAN2) or a USB Ethernet adapter (eth0 in the device info).
5.2.1

Network settings

On the JUMO variTRON 500, the network settings are configured using the device display.
Process:
1. Unlock the configuration: Menu > User management > Log in
a) Select user (e.g. master).
b) Enter password.
The configuration will be unlocked.
2. Configure IP parameters for LAN1 (use IP address as in IO controller).
a) Set method (manual IP/automatic IP via DHCP):
Menu > Configuration > Ethernet > LAN1 > Method:
Select Manual.
b) Set IP address (as in the IO controller; required for project planning):
Menu > Configuration > Ethernet > LAN1 > IP address:
Enter IP address (for example 192.168.0.3).
c) Set subnet mask:
Menu > Configuration > Ethernet > LAN1 > Subnet mask:
Enter subnet mask (for example 255.255.255.0).
d) Check and if necessary set standard gateway:
Menu > Configuration > Ethernet > LAN1 > Standard gateway:
Enter 0.0.0.0.
3. Exit configuration by pressing the Back key several times and confirm Save settings.
NOTE!
Check the device information to see whether the IP settings for LAN1 have been correctly applied: Menu
> Device info > Ethernet > LAN1
project
can
also
be
5 Project planning
transferred
directly
from
CODESYS®
into
the
17