Project Planning; Project Integration Of Jumo Io Devices In Codesys - JUMO variTRON 500 Manual

Automation system
Table of Contents

Advertisement

5

Project planning

5.1
Project integration of JUMO IO devices in CODESYS®
This chapter provides a general description of how to integrate a JUMO IO device into an engineering
system such as CODESYS®.
The two subsequent chapters contain detailed instructions for configuring and integrating a JUMO IO
device using the JUMO variTRON 500 by way of example.
chapter 5.2 "Configuring the JUMO IO device", Page 17
chapter 5.3 "Project integration of JUMO IO device into IO controller", Page 26
NOTE!
The JUMO IO device uses the little endian format – please note this when configuring the IO controller
and set it if required. Otherwise the transferred data will not be interpreted correctly!
For JUMO field devices to be integrated into the project structure of the IO controller as an IO device,
the GSDML file of the respective device must be imported into the engineering system of your IO con-
troller. The GSDML file describes all PROFINET IO features of IO devices and delivers to the engineer-
ing system all the information required for the project planning phase. This file is located on the DVD
from the scope of delivery of your JUMO field device, or can alternatively be downloaded from the JUMO
website. Once the GSDML file has been imported into the engineering system, the corresponding field
device is available as an IO device in the engineering system (e.g. "Hardware catalog" for SIMATIC® or
"Device repository" for CODESYS®), and can be incorporated into the hardware structure of your proj-
ects. With JUMO IO devices, modules can then be added as slots. In the engineering system, modules
are treated as modular devices for expanding IO devices. They are selected from the engineering sys-
tem catalog and assigned to the slots in the JUMO IO device. The procedure for integrating devices into
project structures is described in the documentation for the engineering system of your IO controller.
Process
1. Import the GSDML file of your JUMO IO device into the engineering system of your IO controller.
NOTE!
The GSDML file for the current device version is located on the DVD from the scope of delivery of your
JUMO field device. Alternatively, you can download the GSDML file from the JUMO website.
2. Configure the PROFINET modules for your JUMO field device using the setup program (JUMO
smartWARE Setup variTRON).
3. Integrate the desired JUMO field device into the project structure of your IO controller. Make sure the
device software version matches the version data of the JUMO field device integrated into the project
structure.
NOTE!
The exact procedure for integrating PROFINET IO devices can be found in the description of your engi-
neering system.
4. Assign a device name.
NOTE!
Engineering systems offer a function for identifying field devices. If JUMO field devices are addressed
via the "Identification function" of the engineering system, this is signaled by the flashing of the front dis-
play.
5. Set the communication parameters (device name, IP address, etc.) of the JUMO field device in the
project structure of the IO controller.
5 Project planning
15

Advertisement

Table of Contents
loading

Table of Contents