Operating Instructions
Micropilot FMR63B
PROFINET with Ethernet-APL
Free space radar
Solutions
Services

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Micropilot FMR63B and is the answer not in the manual?

Questions and answers

Darrel Doggett
February 19, 2025

calibration

1 comments:
Mr. Anderson
May 14, 2025

To calibrate the Endress+Hauser FMR63B, use the Commissioning wizard available in FieldCare, DeviceCare, SmartBlue, or on the device display. The wizard guides you step-by-step through the initial setup. Enter the correct values or select options for each parameter. If the medium has a low dielectric constant (εr < 2), adjust the zero point to a distance C above the tank floor to avoid reduced accuracy. Calibration involves setting the "Empty calibration" (0%) and "Full calibration" (100%) parameters.

This answer is automatically generated

Subscribe to Our Youtube Channel

Summary of Contents for Endress+Hauser Micropilot FMR63B

  • Page 1 Products Solutions Services BA02268F/00/EN/01.23-00 71610087 2023-04-22 01.00.zz (Device firmware) Operating Instructions Micropilot FMR63B PROFINET with Ethernet-APL Free space radar advanced physical layer...
  • Page 2 The manufacturer reserves the right to modify technical data without prior notice. The Endress+Hauser sales organization will supply you with current information and updates to these instructions. Endress+Hauser...
  • Page 3: Table Of Contents

    Micropilot FMR63B PROFINET with Ethernet-APL Table of contents Table of contents 5.3.3 Antenna, PTFE cladded, flush mount About this document ....5 80 mm (3 in) ....
  • Page 4 Table of contents Micropilot FMR63B PROFINET with Ethernet-APL 11.7 Event logbook ......56 System integration ....39 11.7.1 Event history .
  • Page 5: About This Document

    Micropilot FMR63B PROFINET with Ethernet-APL About this document About this document Purpose of this document These Operating Instructions contain all the information that is required in the various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
  • Page 6: Terms And Abbreviations

    Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners. Apple®...
  • Page 7 Micropilot FMR63B PROFINET with Ethernet-APL About this document KALREZ®, VITON® Registered trademarks of DuPont Performance Elastomers L.L.C., Wilmington, DE USA TRI-CLAMP® Registered trademark of Ladish & Co., Inc., Kenosha, USA Endress+Hauser...
  • Page 8: Basic Safety Instructions

    Do not touch or clean device surfaces with pointed or hard objects. Clarification of borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.
  • Page 9: Workplace Safety

    It meets the general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions.
  • Page 10: Protecting Access Via A Password

    Basic safety instructions Micropilot FMR63B PROFINET with Ethernet-APL • Write protection via hardware write protection switch • Access code to change user role (applies to operation via display, Bluetooth or FieldCare, DeviceCare, asset management tools (e.g., AMS, PDM and Web server)
  • Page 11 Micropilot FMR63B PROFINET with Ethernet-APL Basic safety instructions  Description of device parameters. Endress+Hauser...
  • Page 12: Product Description

    Product description Micropilot FMR63B PROFINET with Ethernet-APL Product description Product design A0046663  1 Design of the Micropilot FMR63B Electronics housing Integrated antenna, PEEK, 20 mm (0.75 in), thread Integrated antenna, PEEK, 20 mm (0.75 in), M24 adapter Antenna, cladded flush mount, PTFE, with Tri-Clamp ISO2852...
  • Page 13: Incoming Acceptance And Product

     All the information about the measuring device is displayed. ‣ Endress+Hauser Operations app; manually enter the serial number indicated on the nameplate or scan the 2D matrix code on the nameplate.  All the information about the measuring device is displayed.
  • Page 14: Manufacturer Address

    Incoming acceptance and product identification Micropilot FMR63B PROFINET with Ethernet-APL 4.2.2 Manufacturer address Endress+Hauser SE+Co. KG Hauptstraße 1 79689 Maulburg, Germany Place of manufacture: See nameplate. Storage and transport 4.3.1 Storage conditions • Use the original packaging • Store the device in clean and dry conditions and protect from damage caused by shocks Storage temperature range See Technical Information.
  • Page 15: Mounting

    Micropilot FMR63B PROFINET with Ethernet-APL Mounting Mounting General instructions WARNING Loss of protection rating if the device is opened in a wet environment. ‣ Only open the device in a dry environment! 1. Install the device or turn the housing so that the cable entries do not point upwards.
  • Page 16: Avoiding Interference Echoes

    Mounting Micropilot FMR63B PROFINET with Ethernet-APL 5.2.2 Avoiding interference echoes A0031813 Metal deflector plates, installed at an angle to scatter the radar signals, help prevent interference echoes. 5.2.3 Vertical alignment of antenna axis Align the antenna so that it is perpendicular to the product surface.
  • Page 17: Antenna, Ptfe Cladded, Flush Mount 50 Mm (2 In)

    Micropilot FMR63B PROFINET with Ethernet-APL Mounting Maximum nozzle length H as a function of the nozzle diameter D D 40 to 50 mm (1.6 to 2 in) 200 mm (8 in) 50 to 80 mm (2 to 3.2 in) 300 mm (12 in) 80 to 100 mm (3.2 to 4 in)
  • Page 18: Turning The Housing

    Mounting Micropilot FMR63B PROFINET with Ethernet-APL The maximum length of the nozzle H depends on the nozzle diameter D D 80 to 100 mm (3.2 to 4 in) 1 750 mm (70 in) 100 to 150 mm (4 to 6 in) 2 200 mm (88 in) ≥...
  • Page 19: Changing The Installation Position Of The Display Module

    Micropilot FMR63B PROFINET with Ethernet-APL Mounting 4 0.7 Nm A0038224 1. If fitted: release the screw of the cover lock for the electronics compartment cover using the Allen key. 2. Unscrew the electronics compartment cover from the transmitter housing and check the cover seal.
  • Page 20 Mounting Micropilot FMR63B PROFINET with Ethernet-APL WARNING Supply voltage switched on! Risk of electric shock and/or explosion! ‣ Switch off the supply voltage before opening the measuring device. 1 → 2 → 3 → 4 mm 0.7 Nm A0046831 A0046832 A0046833 ‣...
  • Page 21: Closing The Housing Covers

    Micropilot FMR63B PROFINET with Ethernet-APL Mounting 7 → A0048406 A0046928 ‣ ‣ Plug in the connection for the Screw the display cover firmly display module in the back onto the housing. If fitted: connection compartment. tighten the screw of the cover ‣...
  • Page 22: Electrical Connection

    Electrical connection Micropilot FMR63B PROFINET with Ethernet-APL Electrical connection Connecting requirements 6.1.1 Cover with securing screw In the case of devices for use in the hazardous area with a certain type of protection, the cover is sealed by a securing screw.
  • Page 23: Connecting The Device

    Micropilot FMR63B PROFINET with Ethernet-APL Electrical connection A0046583 Single compartment housing, plastic Single compartment housing, aluminum Single compartment housing, 316L hygiene (Ex device) Dual compartment housing Dual compartment housing, L-form Ground terminal for connecting the potential matching line WARNING Explosion Hazard! ‣...
  • Page 24: Cable Specification

    Electrical connection Micropilot FMR63B PROFINET with Ethernet-APL 6.2.2 Cable specification Rated cross-section • Supply voltage 0.5 to 2.5 mm (20 to 13 AWG) • Protective earth or grounding of the cable shield > 1 mm (17 AWG) • External ground terminal 0.5 to 4 mm...
  • Page 25: Wiring

    Micropilot FMR63B PROFINET with Ethernet-APL Electrical connection Overvoltage category Overvoltage category II 6.2.4 Wiring WARNING Supply voltage might be connected! Risk of electric shock and/or explosion! ‣ If the device is used in hazardous areas, make sure to comply with national standards and the specifications in the Safety Instructions (XAs).
  • Page 26: Terminal Assignment

    Electrical connection Micropilot FMR63B PROFINET with Ethernet-APL 6.2.5 Terminal assignment Single compartment housing A0042594  4 Connection terminals and ground terminal in the connection compartment Positive terminal Negative terminal Internal ground terminal Dual compartment housing A0042803  5 Connection terminals and ground terminal in the connection compartment...
  • Page 27: Cable Entries

    Micropilot FMR63B PROFINET with Ethernet-APL Electrical connection Dual compartment housing, L-form A0045842  6 Connection terminals and ground terminal in the connection compartment Positive terminal Negative terminal Internal ground terminal 6.2.6 Cable entries A0046584 Single compartment housing, plastic Single compartment housing, aluminum...
  • Page 28: Ensuring The Degree Of Protection

    Electrical connection Micropilot FMR63B PROFINET with Ethernet-APL Devices with M12 plug A0011175  7 View of the plug-in connection on the device APL signal - APL signal + Shielding Not assigned Various M12 sockets are available as accessories for devices with M12 plugs.
  • Page 29: Operation Options

    • Operation via Bluetooth® wireless technology (with optional device display with Bluetooth) with SmartBlue app or FieldXpert, DeviceCare • Operation via Web server • Operation via operating tool (Endress+Hauser FieldCare/DeviceCare) or FDI Hosts (e.g., PDM) Operating keys and DIP switches on the electronic...
  • Page 30: Access To Operating Menu Via Local Display

    • Press and hold the keys simultaneously to return to the upper level 7.4.2 Operation via Bluetooth® wireless technology (optional) Prerequisite • Device with device display including Bluetooth • Smartphone or tablet with Endress+Hauser SmartBlue app or PC with DeviceCare from version 1.07.05 or FieldXpert SMT70 Endress+Hauser...
  • Page 31: Access To Operating Menu Via Web Browser

    Micropilot FMR63B PROFINET with Ethernet-APL Operation options The connection has a range of up to 25 m (82 ft). The range can vary depending on environmental conditions such as attachments, walls or ceilings. The operating keys on the display are locked as soon as the device is connected via Bluetooth.
  • Page 32: Requirements

    Operation options Micropilot FMR63B PROFINET with Ethernet-APL 7.5.2 Requirements Computer software Recommended operating systems • Microsoft Windows 7 or higher. • Mobile operating systems: • iOS • Android Microsoft Windows XP is supported. Web browsers supported • Microsoft Internet Explorer 8 or higher •...
  • Page 33: Establishing A Connection

    Micropilot FMR63B PROFINET with Ethernet-APL Operation options 7.5.3 Establishing a connection Via PROFINET with Ethernet-APL network A0046097  10 Options for remote operation via PROFINET with Ethernet-APL network: star topology Automation system, e.g., Simatic S7 (Siemens) Ethernet switch Computer with Web browser (e.g., Microsoft Edge) for accessing the integrated device Web server or computer with operating tool (e.g., FieldCare, DeviceCare, SIMATIC PDM) with iDTM Profinet Communication...
  • Page 34: User Interface

    Operation options Micropilot FMR63B PROFINET with Ethernet-APL A0046626  11 Web browser login Device tag Device name Status signal Locking status Current measured values Select the language Enter the "Password" parameter Login 1. Select the preferred Language parameter for the Web browser.
  • Page 35: Disabling The Web Server

    Micropilot FMR63B PROFINET with Ethernet-APL Operation options Header The following information appears in the header: • Device tag • Device name • Status signal • Locking status • Current measured values Navigation area If a function is selected in the function bar, the submenus of the function open in the navigation area.
  • Page 36: Logging Out

    Operation options Micropilot FMR63B PROFINET with Ethernet-APL Range of functions of "Web server functionality" parameter Option Description Disable • The Web server is completely disabled. • Port 80 is locked. Enable • The complete functionality of the Web server is available.
  • Page 37: Connecting The Operating Tool

    Micropilot FMR63B PROFINET with Ethernet-APL Operation options 7.6.1 Connecting the operating tool Via PROFINET with Ethernet-APL network A0046097  14 Options for remote operation via PROFINET with Ethernet-APL network: star topology Automation system, e.g., Simatic S7 (Siemens) Ethernet switch Computer with Web browser (e.g., Microsoft Edge) for accessing the integrated device Web server or computer with operating tool (e.g., FieldCare, DeviceCare, SIMATIC PDM) with iDTM Profinet Communication...
  • Page 38: Fieldcare

    7.8.1 Function scope Tool for connecting and configuring Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated "DeviceCare" tool. Together with the device type managers (DTMs), DeviceCare presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S...
  • Page 39: System Integration

    Micropilot FMR63B PROFINET with Ethernet-APL System integration System integration Overview of device description files 8.1.1 Current version data for the device Firmware version 01.00.zz • On the title page of the Operating Instructions • On the transmitter nameplate • System → Information → Firmware version Firmware version parameter release date 04.2023...
  • Page 40: File Name Of The Device Master File (Gsd)

    System integration Micropilot FMR63B PROFINET with Ethernet-APL 8.2.1 File name of the device master file (GSD) Example of the name of a device master file: GSDML-V2.43-EH-Micropilot-202304dd.xml (dd corresponds to the release day) GSDML Description language V2.43 Version of the PROFINET specification...
  • Page 41: Cyclic Data Transmission

    Micropilot FMR63B PROFINET with Ethernet-APL System integration Cyclic data transmission 8.3.1 Overview of the modules The following graphic shows which modules are available to the device for cyclic data exchange. Cyclic data exchange is performed with an automation system. Application → PROFINET → Analog input → Analog input 1 to 11 → Assign process...
  • Page 42: Status Coding

    System integration Micropilot FMR63B PROFINET with Ethernet-APL Module: Binary input The Binary input module can cyclically send discrete values from the device to the automation system. The status of the Heartbeat Verification is transmitted for the device: Module: Binary input Heartbeat Technology slot 80...
  • Page 43: Startup Configuration

    Micropilot FMR63B PROFINET with Ethernet-APL System integration 8.3.4 Startup configuration Startup configuration The automation system adopts the configuration of the most important parameters of the device. (NSU) • Interfaces: • Display operation • Web server functionality • Bluetooth activation • Service (UART-CDI) •...
  • Page 44: Commissioning

    Commissioning Micropilot FMR63B PROFINET with Ethernet-APL Commissioning All configuration tools provide a commissioning assistant that supports the user when setting the most important configuration parameters (Guidance menu Commissioning wizard). Preliminaries The measuring range and the unit in which the measured value is transmitted correspond to the data on the nameplate.
  • Page 45: Via Service Interface (Cdi)

    Via service interface (CDI) A0039148 Computer with FieldCare/DeviceCare operating tool Commubox FXA291 Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface) 9.3.3 Hardware settings Setting the device name A measuring point can be quickly identified within a plant on the basis of the Device tag parameter and PROFINET device name parameter.
  • Page 46: Configuring The Operating Language

    Commissioning Micropilot FMR63B PROFINET with Ethernet-APL Configuring the operating language 9.4.1 Local display Setting the operating language To set the operating language, the display first needs to be unlocked: 1. Press the  key for at least 2 s.  A dialog box appears.
  • Page 47: Configuring The Device

    Micropilot FMR63B PROFINET with Ethernet-APL Commissioning Configuring the device 9.5.1 Level measurement in liquids 100% A0016933  17 Configuration parameters for level measurement in liquids Reference point of measurement Length of antenna + 10 mm (0.4 in) 50 to 80 mm (1.97 to 3.15 in); medium εr < 2...
  • Page 48: Recording The Echo Curve

    Commissioning Micropilot FMR63B PROFINET with Ethernet-APL Recording the Echo curve Record the current Echo curve as a reference echo curve for subsequent diagnostic purposes After the measurement has been configured, it is recommended to record the current Echo curve as a reference echo curve.
  • Page 49: Operation

    Micropilot FMR63B PROFINET with Ethernet-APL Operation Operation 10.1 Reading off the device locking status Displaying active write protection: • In the Locking status parameter Menu path of local display: at the top operating level Menu path of operating tool: System → Device management •...
  • Page 50: Diagnostics And Troubleshooting

    Diagnostics and troubleshooting Micropilot FMR63B PROFINET with Ethernet-APL Diagnostics and troubleshooting 11.1 General troubleshooting 11.1.1 General errors Device is not responding • Possible cause: Supply voltage does not match the specification on the nameplate Remedial action: Apply the correct voltage •...
  • Page 51: Diagnostic Message

    Remedial action: The standard user name is "admin" and the password is the device serial number indicated on the device nameplate (only if the password was not changed by the user beforehand) If the password has been forgotten, contact Endress+Hauser Service (www.addresses.endress.com) Connection via SmartBlue not possible •...
  • Page 52: Diagnostic Information On Local

    Diagnostics and troubleshooting Micropilot FMR63B PROFINET with Ethernet-APL 11.3.1 Diagnostic information on local display A0043759  19 Segment display without keys Status symbol for event level Status signal with diagnostic event X X X X X X X S801 X X X X X X X A0043103 ...
  • Page 53: Diagnostic Event And Event Text

    Micropilot FMR63B PROFINET with Ethernet-APL Diagnostics and troubleshooting 11.3.4 Diagnostic event and event text The fault can be identified by means of the diagnostic event. The event text helps you by providing information about the fault. In addition, the associated status symbol is displayed in front of the diagnostic event.
  • Page 54: Operating Menu

    Diagnostics and troubleshooting Micropilot FMR63B PROFINET with Ethernet-APL 2 → Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2 Diagnostics 3 A0051132 ‣ Select the diagnostic event and confirm Supply voltage (ID:203) S801 0d00h02m25s Increase supply voltage A0051133 ‣ Remedy informationClosing 11.4.2...
  • Page 55 Micropilot FMR63B PROFINET with Ethernet-APL Diagnostics and troubleshooting Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Build-up detected Check process conditions Warning Diagnostic of electronic Real time clock Replace main electronics Warning...
  • Page 56: Event Logbook

    Diagnostics and troubleshooting Micropilot FMR63B PROFINET with Ethernet-APL Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Record map Recording of mapping Warning please wait Diagnostic of process Supply voltage too low Increase supply voltage...
  • Page 57: Filtering The Event Logbook

    Micropilot FMR63B PROFINET with Ethernet-APL Diagnostics and troubleshooting 11.7.2 Filtering the event logbook Filters can be used to determine which category of event messages is displayed in the Event list submenu. Navigation: Diagnostics → Event logbook Filter categories • All •...
  • Page 58: Resetting The Device

    Diagnostics and troubleshooting Micropilot FMR63B PROFINET with Ethernet-APL Info number Info name I1666 Clock synchronized I1712 New flash file received I1956 Reset 11.8 Resetting the device 11.8.1 Reset password via operating tool Enter a code to reset the current ' M aintenance' password.
  • Page 59: Device Information

    Micropilot FMR63B PROFINET with Ethernet-APL Diagnostics and troubleshooting Resetting the device to the factory setting 12 s Display 50 ms A0050015  22 Sequence - Factory setting Reset the device to the factory setting ‣ Press operating key I for at least 12 s.
  • Page 60: Maintenance

    Maintenance Micropilot FMR63B PROFINET with Ethernet-APL Maintenance No special maintenance work is required. 12.1 Exterior cleaning Notes on cleaning • The cleaning agents used should not corrode the surfaces and the seals • Observe the degree of protection of the device 12.2...
  • Page 61: Repair

    Repair concept Endress+Hauser repair concept • The devices have a modular design • Repairs can be carried out by Endress+Hauser Service or by appropriately trained customers • Spare parts are grouped into logical kits with the associated replacement instructions For more information on service and spare parts, please contact your Endress+Hauser sales representative.
  • Page 62: Historom

    Repair Micropilot FMR63B PROFINET with Ethernet-APL 13.3.1 HistoROM It is not necessary to perform a new device calibration after replacing the display or transmitter electronics. The spare part is supplied without HistoROM. After removing the transmitter electronics, remove HistoRom and insert it into the new spare part.
  • Page 63: Accessories

    Micropilot FMR63B PROFINET with Ethernet-APL Accessories Accessories 14.1 Weather protection cover 316L The weather protection cover can be ordered together with the device via the "Accessory enclosed" product structure. It is used to protect against direct sunlight, precipitation and ice.
  • Page 64: M12 Socket

    Accessories Micropilot FMR63B PROFINET with Ethernet-APL Material Plastic Order number for accessories: 71438291 14.3 M12 socket A0051231  25 M12 socket, straight M12 socket, straight • Material: Body: PBT; union nut: nickel-plated die-cast zinc; seal: NBR • Degree of protection (fully locked): IP67 •...
  • Page 65: Remote Display Fhx50B

    Micropilot FMR63B PROFINET with Ethernet-APL Accessories M12 socket, angled, 5 m (16 ft) cable • M12 socket material: • Body: TPU • Union nut: nickel-plated die-cast zinc • Cable material: • Cable Li Y YM 4×0.34 mm (20 AWG) • Cable colors •...
  • Page 66: Gas-Tight Feedthrough

    Accessories Micropilot FMR63B PROFINET with Ethernet-APL Connecting cable: • Connecting cable (option) up to 30 m (98 ft) • Customer-supplied standard cable up to 60 m (197 ft) Recommendation: EtherLine®-P CAT.5e from LAPP. Specification of customer-supplied connecting cable Push-in CAGE CLAMP®, connection technology, push actuation •...
  • Page 67: Technical Data

    Micropilot FMR63B PROFINET with Ethernet-APL Technical data Technical data 15.1 Input Measured variable The measured variable is the distance between the reference point and the product surface. The level is calculated based on "E", the empty distance entered. Measuring range The measuring range starts at the point where the beam hits the tank floor.
  • Page 68 Technical data Micropilot FMR63B PROFINET with Ethernet-APL 100% A0051658  28 Usable measuring range Length of antenna + 10 mm (0.4 in) Usable measuring range 50 to 80 mm (1.97 to 3.15 in); medium εr < 2 Vessel height Reference point of measurement, varies depending on the antenna system For further information on the reference point, see →...
  • Page 69 For the dielectric constants (DC values) of many media commonly used in industry, please refer to: • Dielectric constant (DC value) Compendium CP01076F • The Endress+Hauser "DC Values app" (available for Android and iOS) Measurement in storage vessel Storage vessel - measuring conditions Calm medium surface (e.g.
  • Page 70 Technical data Micropilot FMR63B PROFINET with Ethernet-APL Antenna, PTFE cladded flush mount, 50 mm (2 in) in storage vessel Media group Measuring range A0 (ε 1.2 to 1.4) 7 m (23 ft) A (ε 1.4 to 1.9) 12 m (39 ft) B (ε...
  • Page 71 Micropilot FMR63B PROFINET with Ethernet-APL Technical data Cladded antenna, PEEK, 40 mm (1.5 in) in storage vessel Media group Measuring range A0 (ε 1.2 to 1.4) 3 m (10 ft) A (ε 1.4 to 1.9) 6 m (20 ft) B (ε...
  • Page 72 Technical data Micropilot FMR63B PROFINET with Ethernet-APL Antenna, PTFE cladded flush mount, 80 mm (3 in) in buffer vessel Media group Measuring range A0 (ε 1.2 to 1.4) 12 m (39 ft) A (ε 1.4 to 1.9) 23 m (75 ft) B (ε...
  • Page 73 Micropilot FMR63B PROFINET with Ethernet-APL Technical data Integrated antenna, PEEK, 20 mm (0.75 in) in vessel with agitator Media group Measuring range A (ε 1.4 to 1.9) 1 m (3.3 ft) B (ε 1.9 to 4) 1.5 m (5 ft) C (ε...
  • Page 74: Output

    Technical data Micropilot FMR63B PROFINET with Ethernet-APL Cladded antenna, PEEK, 20 mm (0.75 in) in vessel with agitator Media group Measuring range A (ε 1.4 to 1.9) 1 m (3.3 ft) B (ε 1.9 to 4) 1.5 m (5 ft) C (ε...
  • Page 75 Micropilot FMR63B PROFINET with Ethernet-APL Technical data Operating tool via PROFINET with Ethernet-APL • According to "Application layer protocol for decentralized periphery", Version 2.4 • Diagnostics according to PROFINET PA Profile 4.02 Linearization The linearization function of the device allows the conversion of the measured value into any unit of length, weight, flow or volume.
  • Page 76: Environment

    Technical data Micropilot FMR63B PROFINET with Ethernet-APL Supported functions • Identification & maintenance Simple device identification via: • Control system • Nameplate • Measured value status The process variables are communicated with a measured value status • Blinking feature via the local display for simple device identification and assignment •...
  • Page 77 Micropilot FMR63B PROFINET with Ethernet-APL Technical data Plastic housing Plastic housing; process temperature –20 to +150 °C (–4 to +302 °F) A0032024  29 Plastic housing; process temperature –20 to +150 °C (–4 to +302 °F) = T : –20 °C (–4 °F) |  T : +76 °C (+169 °F)
  • Page 78 Technical data Micropilot FMR63B PROFINET with Ethernet-APL Plastic housing; process temperature –20 to +200 °C (–4 to +392 °F) A0032024  31 Plastic housing; process temperature –20 to +200 °C (–4 to +392 °F) = T : –20 °C (–4 °F) |  T : +76 °C (+169 °F)
  • Page 79 Micropilot FMR63B PROFINET with Ethernet-APL Technical data Restriction to a process temperature of 0 to +150 °C (+32 to +302 °F) with CSA C/US approval and plastic housing A0048826  34 Plastic housing; process temperature 0 to +150 °C (+32 to +302 °F) with CSA C/US approval = T...
  • Page 80 Technical data Micropilot FMR63B PROFINET with Ethernet-APL Aluminum housing, coated Aluminum housing; process temperature –20 to +150 °C (–4 to +302 °F) A0032024  37 Aluminum housing, coated; process temperature –20 to +150 °C (–4 to +302 °F) = T : –20 °C (–4 °F) |  T : +79 °C (+174 °F)
  • Page 81 Micropilot FMR63B PROFINET with Ethernet-APL Technical data Aluminum housing; process temperature –40 to +200 °C (–40 to +392 °F) A0032024  40 Aluminum housing, coated; process temperature –40 to +200 °C (–40 to +392 °F) = T : –40 °C (–40 °F) |  T : +79 °C (+174 °F)
  • Page 82 Technical data Micropilot FMR63B PROFINET with Ethernet-APL 316L housing; process temperature –40 to +150 °C (–40 to +302 °F) A0032024  43 316L housing; process temperature range: –40 to +150 °C (–40 to +302 °F) = T : –40 °C (–40 °F) |  T : +77 °C (+171 °F)
  • Page 83 Micropilot FMR63B PROFINET with Ethernet-APL Technical data 316L housing, hygiene; process temperature –20 to +200 °C (–4 to +392 °F) A0032024  46 316L housing, hygiene; process temperature –20 to +200 °C (–4 to +392 °F) = T : –20 °C (–4 °F) |  T : +76 °C (+169 °F)
  • Page 84 Technical data Micropilot FMR63B PROFINET with Ethernet-APL Installation height as per Generally up to 5 000 m (16 404 ft) above sea level IEC61010-1 Ed.3 Degree of protection Test as per IEC 60529 and NEMA 250-2014 Housing IP66/68, NEMA TYPE 4X/6P IP68 test condition: 1.83 m under water for 24 hours.
  • Page 85: Process

    Micropilot FMR63B PROFINET with Ethernet-APL Technical data 15.4 Process Process pressure range WARNING The maximum pressure for the device depends on the lowest-rated component with regard to pressure (components are: process connection, optional mounted parts or accessories). ‣ Only operate the device within the specified limits for the components! ‣...
  • Page 86 –1 to 25 bar (–14.5 to 362.6 psi) A0047825 The pressure range may be further restricted in the event of a CRN approval. Dielectric constant For liquids ε ≥  1.2 Contact Endress+Hauser for applications with lower dielectric constants than indicated. Endress+Hauser...
  • Page 87: Index

    Micropilot FMR63B PROFINET with Ethernet-APL Index Index Symbols "Device ID" parameter ......39 Media ........8 "Device revision"...
  • Page 88 *71610087* 71610087 www.addresses.endress.com...