Summary of Contents for Endress+Hauser Micropilot FMR67B
Page 1
Products Solutions Services KA01615F/00/EN/02.24-00 71687759 2024-12-06 Brief Operating Instructions Micropilot FMR67B Free-space radar PROFINET over Ethernet-APL advanced physical layer These Brief Operating Instructions are not a substitute for the Operating Instructions pertaining to the device. Detailed information can be found in the Operating Instructions and the additional documentation.
Page 2
Micropilot FMR67B PROFINET over Ethernet-APL Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
Micropilot FMR67B PROFINET over Ethernet-APL Symbols Symbols Safety symbols DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
Requirements for the personnel Micropilot FMR67B PROFINET over Ethernet-APL Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
Do not touch or clean device surfaces with pointed or hard objects. Clarification of borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.
All the information about the measuring device is displayed. ‣ Endress+Hauser Operations app; manually enter the serial number indicated on the nameplate or scan the 2D matrix code on the nameplate. All the information about the measuring device is displayed.
Micropilot FMR67B PROFINET over Ethernet-APL Storage and transport • Technical values, e.g. supply voltage, current consumption, ambient temperature, communication-specific data (optional) • Degree of protection • Approvals with symbols • Reference to Safety Instructions (XA) (optional) ‣ Compare the information on the nameplate with the order.
Installation Micropilot FMR67B PROFINET over Ethernet-APL Installation 11.1 General instructions WARNING Loss of protection rating if the device is opened in a wet environment. ‣ Only open the device in a dry environment! Install the device or turn the housing so that the cable entries do not point upwards.
Micropilot FMR67B PROFINET over Ethernet-APL Installation 11.2 Installation requirements 11.2.1 Internal vessel fittings A0031814 Avoid internal fittings (level switches, temperature sensors, struts, vacuum rings, heating coils, baffles etc.) inside the signal beam. Pay attention to the beam angle α. 11.2.2 Vertical alignment of antenna axis Align the antenna so that it is perpendicular to the product surface.
Page 10
Installation Micropilot FMR67B PROFINET over Ethernet-APL Maximum nozzle length H as a function of the nozzle diameter D D 80 to 100 mm (3.2 to 4 in) 1 700 mm (67 in) 100 to 150 mm (4 to 6 in) 2 100 mm (83 in) ≥...
Page 11
Micropilot FMR67B PROFINET over Ethernet-APL Installation Information about the mounting nozzle The maximum nozzle length H depends on the nozzle diameter D. The maximum nozzle length H depends on the nozzle diameter D D 80 to 100 mm (3.2 to 4 in)
Page 12
Installation Micropilot FMR67B PROFINET over Ethernet-APL The maximum length of the nozzle H depends on the nozzle diameter D D 50 to 80 mm (2 to 3.2 in) 750 mm (30 in) 80 to 100 mm (3.2 to 4 in)
Page 13
Micropilot FMR67B PROFINET over Ethernet-APL Installation 11.3.5 Antenna flush mount 80 mm (3 in) with alignment unit UNI flanges with an integrated alignment unit are available for the antenna flush mount 80 mm (3 in). An inclination of the antenna axis of up to 15 ° in all directions can be set with the help of the alignment unit.
Page 14
Installation Micropilot FMR67B PROFINET over Ethernet-APL 11.3.6 Purge air connection In applications with strong dust emissions, the integrated purge air connection can prevent the antenna from becoming clogged. Pulse operation is recommended. A0046593 3 Antenna with purge air adapter Purge air connection NPT 1/4"...
Page 15
Micropilot FMR67B PROFINET over Ethernet-APL Installation A0046660 Plastic single compartment housing (no locking screw) Aluminum single compartment housing Single compartment housing, 316L, hygiene (no locking screw) Dual compartment housing Dual compartment housing, L-form Locking screw NOTICE The housing cannot be unscrewed fully.
Electrical connection Micropilot FMR67B PROFINET over Ethernet-APL Unscrew the electronics compartment cover from the transmitter housing and check the cover seal. Press the release mechanism and remove the display module. Turn the display module to the desired position: maximum 4 × 90 ° in each direction. Fit the display module on the electronics compartment in the desired position until it clicks into place.
Page 17
Micropilot FMR67B PROFINET over Ethernet-APL Electrical connection NOTICE If the securing screw is not positioned correctly, the cover cannot provide secure sealing. ‣ Open the cover: slacken the screw of the cover lock with a maximum of 2 turns so that the screw does not fall out.
Page 18
Electrical connection Micropilot FMR67B PROFINET over Ethernet-APL A0046583 Single compartment housing, plastic Single compartment housing, aluminum, coated Single compartment housing, 316L, hygiene (Ex device) Dual compartment housing, aluminum, coated Dual compartment housing, L-shaped, aluminum, coated Ground terminal for connecting the potential matching line WARNING Ignitable sparks or impermissible high surface temperatures.
Micropilot FMR67B PROFINET over Ethernet-APL Electrical connection 12.2 Connecting the device A0046659 Single compartment housing, plastic Single compartment housing, aluminum, coated Single compartment housing, 316L, hygiene Dual compartment housing, aluminum, coated Dual compartment housing, L-shaped, aluminum, coated Connection compartment cover Devices with a single compartment 316L hygiene housing and conduit screw connection must be connected as end-of-line devices;...
Page 20
Electrical connection Micropilot FMR67B PROFINET over Ethernet-APL Cable outer diameter The cable outer diameter depends on the cable gland used • Coupling, plastic: ⌀5 to 10 mm (0.2 to 0.38 in) • Coupling, nickel-plated brass: ⌀7 to 10.5 mm (0.28 to 0.41 in) •...
Page 21
Micropilot FMR67B PROFINET over Ethernet-APL Electrical connection 12.2.4 Wiring WARNING Supply voltage might be connected! Risk of electric shock and/or explosion! ‣ If the device is used in hazardous areas, make sure to comply with national standards and the specifications in the Safety Instructions (XAs). The specified cable gland must be used.
Page 22
Electrical connection Micropilot FMR67B PROFINET over Ethernet-APL 12.2.5 Terminal assignment Single compartment housing A0042594 6 Connection terminals and ground terminal in the connection compartment, single compartment housing Positive terminal Negative terminal Internal ground terminal Dual compartment housing A0042803 7...
Page 23
Micropilot FMR67B PROFINET over Ethernet-APL Electrical connection Dual compartment housing, L-shaped A0045842 8 Connection terminals and ground terminal in the connection compartment Plus terminal Minus terminal Internal ground terminal 12.2.6 Cable entries A0046584 Single compartment housing, plastic Single compartment housing, aluminum, coated...
Electrical connection Micropilot FMR67B PROFINET over Ethernet-APL 12.2.7 Available device plug connectors In the case of devices with a plug, it is not necessary to open the housing for connection purposes. Use the enclosed seals to prevent the penetration of moisture into the device.
• Operation via Bluetooth® wireless technology (with optional device display with Bluetooth) with SmartBlue app or FieldXpert, DeviceCare • Operation via Web server • Operation via operating tool (Endress+Hauser FieldCare/DeviceCare) or FDI Hosts (e.g., PDM) 13.2 Operating keys and DIP switches on the electronic insert...
Page 26
Operation options Micropilot FMR67B PROFINET over Ethernet-APL 13.3.1 User roles and related access authorization The two user roles Operator and Maintenance (as-delivered state) have different write access to the parameters if a device-specific access code has been defined. This access code protects the device configuration from unauthorized access.
Page 27
Prerequisite • Device with device display including Bluetooth • Smartphone or tablet with Endress+Hauser SmartBlue app or PC with DeviceCare from version 1.07.05 or FieldXpert SMT70 The connection has a range of up to 25 m (82 ft). The range can vary depending on environmental conditions such as attachments, walls or ceilings.
Page 28
• Like the password, the reset code can also be changed. • If the user-defined reset code is lost, the password can no longer be reset via the SmartBlue app. In this case, contact Endress+Hauser Service. 13.5 Access to operating menu via web browser 13.5.1...
Page 29
Micropilot FMR67B PROFINET over Ethernet-APL Operation options 13.5.2 Prerequisites Computer software Recommended operating systems • Microsoft Windows 7 or higher. • Mobile operating systems: • iOS • Android Microsoft Windows XP is supported. Web browsers supported • Microsoft Internet Explorer 8 or higher •...
Page 30
Operation options Micropilot FMR67B PROFINET over Ethernet-APL A0046626 12 Web browser login Device tag Device name Status signal Locking status Current measured values Select the language Enter the "Password" parameter Login Select the preferred Language parameter for the Web browser.
Page 31
Micropilot FMR67B PROFINET over Ethernet-APL Operation options 13.5.4 User interface A0052432 13 User interface with sample contents Header Working area Navigation area Header The following information appears in the header: • Device tag • Device name • Status signal •...
Page 32
Operation options Micropilot FMR67B PROFINET over Ethernet-APL Adopting a value 14 Example of Enter button Enter button in the operating tool The value entered is only adopted by pressing the Enter key or clicking on the Enter button (1).
Page 33
Connecting the operating tool Service interface A0039148 Computer with FieldCare/DeviceCare operating tool Commubox FXA291 Service interface (CDI) of the device (= Endress+Hauser Common Data Interface) To update (flash) the device firmware, the device must be powered via the power supply terminals. 13.7 FieldCare 13.7.1...
13.8.1 Function scope Tool for connecting and configuring Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated "DeviceCare" tool. Together with the device type managers (DTMs), DeviceCare presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S...
Page 35
Computer with web browser or with operating tool (e.g.,, DeviceCare) Automation system Field Xpert SMT70 Mobile handheld terminal Local operation via display module 14.3.2 Via service interface (CDI) A0039148 Computer with FieldCare/DeviceCare operating tool Commubox Service interface (CDI) of the device (= Endress+Hauser Common Data Interface) Endress+Hauser...
Page 36
Commissioning Micropilot FMR67B PROFINET over Ethernet-APL 14.4 Configuring the operating language 14.4.1 Local display Setting the operating language To set the operating language, the display first needs to be unlocked: Press the key for at least 2 s. A dialog box appears.
Micropilot FMR67B PROFINET over Ethernet-APL Commissioning 14.5 Configuring the device 14.5.1 Level measurement in bulk solids 100% A0016934 16 Configuration parameters for level measurement in bulk solids Reference point of measurement Length of antenna + 10 mm (0.4 in) Distance Level "Empty calibration"...