Summary of Contents for Endress+Hauser Micropilot FMR62B
Page 1
Products Solutions Services KA01612F/00/EN/02.24-00 71687756 2024-12-06 Brief Operating Instructions Micropilot FMR62B Free-space radar PROFINET over Ethernet-APL advanced physical layer These Brief Operating Instructions are not a substitute for the Operating Instructions pertaining to the device. Detailed information can be found in the Operating Instructions and the additional documentation.
Page 2
Micropilot FMR62B PROFINET over Ethernet-APL Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
Micropilot FMR62B PROFINET over Ethernet-APL Symbols Symbols Safety symbols DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
Requirements for the personnel Micropilot FMR62B PROFINET over Ethernet-APL Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
Do not touch or clean device surfaces with pointed or hard objects. Clarification of borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.
All the information about the measuring device is displayed. ‣ Endress+Hauser Operations app; manually enter the serial number indicated on the nameplate or scan the 2D matrix code on the nameplate. All the information about the measuring device is displayed.
Micropilot FMR62B PROFINET over Ethernet-APL Storage and transport • Technical values, e.g. supply voltage, current consumption, ambient temperature, communication-specific data (optional) • Degree of protection • Approvals with symbols • Reference to Safety Instructions (XA) (optional) ‣ Compare the information on the nameplate with the order.
Installation Micropilot FMR62B PROFINET over Ethernet-APL Installation 11.1 General instructions WARNING Loss of protection rating if the device is opened in a wet environment. ‣ Only open the device in a dry environment! Install the device or turn the housing so that the cable entries do not point upwards.
Micropilot FMR62B PROFINET over Ethernet-APL Installation 11.2 Installation requirements 11.2.1 Internal vessel fittings α A0031777 Avoid internal fittings (level switches, temperature sensors, struts, vacuum rings, heating coils, baffles etc.) inside the signal beam. Pay attention to the beam angle α.
Page 10
Installation Micropilot FMR62B PROFINET over Ethernet-APL Maximum nozzle length H as a function of the nozzle diameter D D 80 to 100 mm (3.2 to 4 in) 1 700 mm (67 in) 100 to 150 mm (4 to 6 in) 2 100 mm (83 in) ≥...
Micropilot FMR62B PROFINET over Ethernet-APL Installation The maximum length of the nozzle H depends on the nozzle diameter D D 50 to 80 mm (2 to 3.2 in) 750 mm (30 in) 80 to 100 mm (3.2 to 4 in)
Page 12
Installation Micropilot FMR62B PROFINET over Ethernet-APL Flange size Number of screws Tightening torque 10K 50A 40 to 60 Nm Information about the mounting nozzle The maximum nozzle length H depends on the nozzle diameter D. The maximum length of the nozzle H depends on the nozzle diameter D D...
Page 13
Micropilot FMR62B PROFINET over Ethernet-APL Installation Flange size Number of screws Tightening torque DN80 PN10/16 40 to 55 Nm DN80 PN25/40 40 to 55 Nm DN100 PN10/16 40 to 60 Nm DN100 PN25/40 55 to 80 Nm DN150 PN10/16 75 to 105 Nm ASME NPS 3"...
Installation Micropilot FMR62B PROFINET over Ethernet-APL The maximum length of the nozzle H depends on the nozzle diameter D D 80 to 100 mm (3.2 to 4 in) 1 750 mm (70 in) 100 to 150 mm (4 to 6 in) 2 200 mm (88 in) ≥...
Page 15
Micropilot FMR62B PROFINET over Ethernet-APL Installation NOTICE The housing cannot be unscrewed fully. ‣ Loosen the external locking screw by a maximum of 1.5 turns. If the screw is unscrewed too much or completely (beyond the screw anchor point), small parts (counter disk) can become loose and fall out.
Electrical connection Micropilot FMR62B PROFINET over Ethernet-APL 11.3.7 Closing the housing covers NOTICE Thread and housing damaged from dirt! ‣ Remove dirt (e.g. sand) on the cover and housing thread. ‣ If you encounter resistance when closing the cover, check the thread for dirt and clean it.
Micropilot FMR62B PROFINET over Ethernet-APL Electrical connection 0.7 Nm A0039520 1 Cover with securing screw 0.7 Nm A0050983 2 Cover with securing screw; hygienic housing (only for dust explosion protection) 12.1.2 Potential equalization The protective ground on the device must not be connected. If necessary, the potential matching line can be connected to the outer ground terminal of the housing before the device is connected.
Electrical connection Micropilot FMR62B PROFINET over Ethernet-APL WARNING Ignitable sparks or impermissible high surface temperatures. Explosion hazard! ‣ Please refer to the separate documentation on applications in hazardous areas for the safety instructions. For optimum electromagnetic compatibility: • Keep potential matching line as short as possible •...
Page 19
Micropilot FMR62B PROFINET over Ethernet-APL Electrical connection 12.2.2 Cable specification Rated cross-section • Supply voltage 0.5 to 2.5 mm (20 to 13 AWG) • Protective earth or grounding of the cable shield > 1 mm (17 AWG) • External ground terminal 0.5 to 4 mm...
Page 20
Electrical connection Micropilot FMR62B PROFINET over Ethernet-APL 12.2.4 Wiring WARNING Supply voltage might be connected! Risk of electric shock and/or explosion! ‣ If the device is used in hazardous areas, make sure to comply with national standards and the specifications in the Safety Instructions (XAs). The specified cable gland must be used.
Micropilot FMR62B PROFINET over Ethernet-APL Electrical connection 12.2.7 Available device plug connectors In the case of devices with a plug, it is not necessary to open the housing for connection purposes. Use the enclosed seals to prevent the penetration of moisture into the device.
• Operation via Bluetooth® wireless technology (with optional device display with Bluetooth) with SmartBlue app or FieldXpert, DeviceCare • Operation via Web server • Operation via operating tool (Endress+Hauser FieldCare/DeviceCare) or FDI Hosts (e.g., PDM) 13.2 Operating keys and DIP switches on the electronic insert...
Page 25
Micropilot FMR62B PROFINET over Ethernet-APL Operation options 13.3.1 User roles and related access authorization The two user roles Operator and Maintenance (as-delivered state) have different write access to the parameters if a device-specific access code has been defined. This access code protects the device configuration from unauthorized access.
Page 26
Prerequisite • Device with device display including Bluetooth • Smartphone or tablet with Endress+Hauser SmartBlue app or PC with DeviceCare from version 1.07.05 or FieldXpert SMT70 The connection has a range of up to 25 m (82 ft). The range can vary depending on environmental conditions such as attachments, walls or ceilings.
Page 27
• Like the password, the reset code can also be changed. • If the user-defined reset code is lost, the password can no longer be reset via the SmartBlue app. In this case, contact Endress+Hauser Service. 13.5 Access to operating menu via web browser 13.5.1...
Page 28
Operation options Micropilot FMR62B PROFINET over Ethernet-APL 13.5.2 Prerequisites Computer software Recommended operating systems • Microsoft Windows 7 or higher. • Mobile operating systems: • iOS • Android Microsoft Windows XP is supported. Web browsers supported • Microsoft Internet Explorer 8 or higher •...
Page 29
Micropilot FMR62B PROFINET over Ethernet-APL Operation options A0046626 9 Web browser login Device tag Device name Status signal Locking status Current measured values Select the language Enter the "Password" parameter Login Select the preferred Language parameter for the Web browser.
Page 30
Operation options Micropilot FMR62B PROFINET over Ethernet-APL 13.5.4 User interface A0052432 10 User interface with sample contents Header Working area Navigation area Header The following information appears in the header: • Device tag • Device name • Status signal •...
Page 31
Micropilot FMR62B PROFINET over Ethernet-APL Operation options Adopting a value 11 Example of Enter button Enter button in the operating tool The value entered is only adopted by pressing the Enter key or clicking on the Enter button (1).
Connecting the operating tool Service interface A0039148 Computer with FieldCare/DeviceCare operating tool Commubox FXA291 Service interface (CDI) of the device (= Endress+Hauser Common Data Interface) To update (flash) the device firmware, the device must be powered via the power supply terminals. 13.7 FieldCare 13.7.1...
13.8.1 Function scope Tool for connecting and configuring Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated "DeviceCare" tool. Together with the device type managers (DTMs), DeviceCare presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S...
Page 34
Computer with web browser or with operating tool (e.g.,, DeviceCare) Automation system Field Xpert SMT70 Mobile handheld terminal Local operation via display module 14.3.2 Via service interface (CDI) A0039148 Computer with FieldCare/DeviceCare operating tool Commubox Service interface (CDI) of the device (= Endress+Hauser Common Data Interface) Endress+Hauser...
Page 35
Micropilot FMR62B PROFINET over Ethernet-APL Commissioning 14.4 Configuring the operating language 14.4.1 Local display Setting the operating language To set the operating language, the display first needs to be unlocked: Press the key for at least 2 s. A dialog box appears.
Commissioning Micropilot FMR62B PROFINET over Ethernet-APL 14.5 Configuring the device 14.5.1 Level measurement in liquids 100% A0016933 13 Configuration parameters for level measurement in liquids Reference point of measurement Length of antenna + 10 mm (0.4 in) 50 to 80 mm (1.97 to 3.15 in); medium εr < 2...
Page 37
Micropilot FMR62B PROFINET over Ethernet-APL Commissioning 14.5.2 Commissioning with the Commissioning wizard In FieldCare, DeviceCare, SmartBlue and on the display, the Commissioning wizard is available to guide the user through the initial commissioning steps. Complete this wizard to commission the device.