5. Check the correct rotation of the fan as on
Page 33, Section 10.1.5.
NOTE: The direct drive fan unit motor can only be
replaced as a complete fan/motor assembly.

Figure 22: Combination Fan/Limit Thermostat

Set Point 3 Limit Temp.
Set Point 2 Fan On
Set Point 1 Fan Off
Fan Terminals
Manual Fan Switch
(White)
Pull out for normal operation.
Push in for continuous fan.
52
I
, C
NSTALLATION
OMMISSIONING
WARNING
Break-off link must be removed from replacement
thermostat.
Heat exchanger damage may result.
Failure to follow these instructions can result in
death, injury, property damage or product damage.
Dial
, O
S
PERATION AND
ERVICE
Fire Hazard
ROBERTS GORDON
BREAK-OFF LINK
thermostats do not have a
MUST BE REMOVED
break-off link. Remove
break-off link if thermostat
was not provided by
Roberts-Gordon.
M
ANUAL
Push Screwdriver in
and hold to release
Push in Lock
Wire to Controlled Equipment
Limit Stat
Manual
Reset Button
(Red)
Limit Terminals
®