14.2 Troubleshooting for Oil Burners (see manufacture's instructions)

START
Assuming fuel & electrical
supplies are ON
Does the burner fire?
Yes
Does the burner control
box 'lockout' before 15
seconds?
No
Does the burner control
box 'lockout' after 15
seconds?
No
Heater Operating
TROUBLESHOOT ENDS.
46
I
, C
NSTALLATION
OMMISSIONING
Check if the control fuse in
No
the heater has blown.
Yes
Disconnect photo cell
Yes
and try again.
Yes
Use Section 14.4 to
trace fault.
Did the burner fire?
Yes
Yes
Use Section 14.4 to
trace fault.
If problems persist, contact
ROBERTS GORDON
No
Tel: +44 (0)121 506 7709
www.rg-inc.com
, O
S
PERATION AND
ERVICE
Do not touch ignition components.
Voltage from ignition components is high.
Failure to follow these instructions can
result in death or electrical shock.
Check supply to burner
No
motor.
Yes
Control box faulty.
No
Repair or replace.
Check ignition electrodes are
set as in the manufacturer's
No
instructions, the fuel supply
and nozzle.
No
Check oil solenoid valve.
®
at
For your safety and optimum heater performance,
use only ROBERTS GORDON
Conduct Commissioning procedure as shown
on Page 33, Section 10.
M
ANUAL
WARNING
Electrical Shock Hazard
Check control box.
No
No
Repair or replace.
®
replacement parts.