ICP DAS USA iSN-101 User Manual page 28

Liquid leak detection module
Hide thumbs Also See for iSN-101:
Table of Contents

Advertisement

@AARAO
Read AI alarm status
iSN-101:
iSN-104:
@AARH
Read all high latch values
@AARHi
Read channel high latch value
@AARL
Read all low latch values
@AARLi
Read channel low latch value
%AANNTTCC
Set configuration FF: bit 6: 1-> checksum enabled
FF
$AAB*
Read open wire status
response
iSN-101:
!AAHH, bit 0 of HH: open wire status, 1 for open wire
iSN-104:
!AAHH, bit 0 to 3 of HH: open wire status, 1 for open wire
$aa0Ci
Span calibration
$aa1Ci
Zero calibration
$aa2
Read configuration
$aa5
Read reset status
$aaF
Read firmware version
$aaI
Read INIT status
$aaM
Read module name
$aaPN
Set Modbus RTU/DCON protocol
$aaP
Read Modbus RTU/DCON protocol
$aaS1
Reload factory calibration parameters
~aaAi
Read ADC raw data
~aaE0
Disable calibration
~aaE1
Enable calibration
~aaI
Soft INIT
iSN-101/104 User Manual
@AARAO
response
!AAHHLL
bit 0 of LL: leak alarm
bit 1 of LL: open wire alarm*
bit 0 to 3 of LL: leak alarm
bit 4 to 7 of LL: open wire alarm