Appendix A: Dcon Command Sets; A-1. Isn-101/104 Dcon Command Sets - ICP DAS USA iSN-101 User Manual

Liquid leak detection module
Hide thumbs Also See for iSN-101:
Table of Contents

Advertisement

Appendix A: DCON Command Sets

A-1. iSN-101/104 DCON Command Sets

Command
Description
#AA
Read All Analog Inputs
response
iSN-101:
iSN-104:
ch2 in k ohm)(resistance of ch3 in k ohm)(threshold index by VR)
#AAi
Read Channel Analog Inputs
iSN-101:
i = 0 for resistance in k ohm, 1 for threshold index by VR
iSN-104:
i = 0 to 3 for channel resistance in k ohm, 4 for threshold index by VR
@AABA
Read beep on alarm time
response
@AABAhh
Set beep on alarm , hh in hex, 0: disabled,
1 ~ 250: beep on alarm time in seconds,
251:beep on alarm continuously
@AACH
Clear all high latch (to current)
@AACHi
Clear channel high latch (to current)
iSN-101:
i = 0 for resistance in k ohm, 1 for threshold index by VR,
iSN-104:
i = 0 to 3 for channel resistance in k ohm, 4 for threshold index by VR,
@AACL
Clear all low latch (to current)
iSN-101/104 User Manual
>(resistance in k ohm)(threshold index by VR)
in engineering format
>(resistance of ch0 in k ohm)(resistance of ch1 in k ohm)(resistance of
in engineering format
!aahh, hh in hex, 0: disabled,
1 ~ 250: beep on alarm time in seconds,
251: beep on alarm continuously
- 26 -