Technical data and dimensions,
Technical data,
HEX 90
Technical data,
HEX 120
22
This table shows the technical data for HEX 90:
Specification
Supply voltage nominal
Cabinet part dimensions (height x width x
depth)
Cabinet part with drain dimensions (height x
width x depth)
Weight
Cooling capacity
Internal airflow, free blowing measurement
External airflow, free blowing measurement
Operating (ambient) temperature range
Relative humidity
Noise level
Environmental protection
Material
This table shows the technical data for HEX 120:
Specification
Supply voltage nominal
Cabinet part dimensions (height x width x
depth)
Cabinet part with drain dimensions (height x
width x depth)
Weight
Cooling capacity
Internal airflow, free blowing measurement
External airflow, free blowing measurement
Operating (ambient) temperature range
Relative humidity
Noise level
Environmental protection
Material
continued
Unit
VDC
mm
mm
kg
W/K
m3/h
m3/h
ºC
%
dB(A)
Unit
VDC
mm
mm
kg
W/K
m3/h
m3/h
ºC
%
dB(A)
Value
48
1227x447x167
1227x447x173
26
90
585
585
-33 - +55
0-99
64
IP 55 from external to
internal air path ac-
cording to EN 60529
0,8 – 2,0 mm aluzinc
coated steel plate
Value
48
1227x598x152
1227x598x167
32
120
620
620
-33 - +55
0-99
64
IP 55 from external to
internal air path ac-
cording to EN 60529
0,8- 2,0 mm aluzinc
coated steel plate