How to replace the external fan,
Procedure,
continued
Step
10
11
12
13
14
15
16
4
Cut the fan cable 20-30 cm from the fan
5
Unscrew the four torx 20
screws (two on each side
of the unit) that hold the
fan suspension
6
Slide the fan suspension a side and wiggle out the faulty fan
7
Place two new rubber nuts at each end of the fan suspension
8
Cut the new fan cable in appropriate length (according to the cut in step 4)
9
Lead the cable up through the fan suspension
Place the fan below the fan suspension
Mount the new fan on the fan suspension with the four torx 20 (from step 5)
Remove the cable insulation, 5 cm on each cable end
Put crimp bushings on all
eight wires
Place shrinkage tubes on
all four wires from the fan
Connect crimped wires,
place shrinkage tubes,
heat tubes
Insulate the cable assem-
bly with vinyl electrical in-
sulation tape and the ca-
ble work is done