PERFORMANCE MADE SMARTER Product manual 9203 Solenoid / alarm driver T E M P E R AT U R E I . S . I N T E R FA C E S CO M M U N I C AT I O N I N T E R FA C E S M U LT I F U N C T I O N A L I S O L AT I O N D I S P L AY...
Page 2
6 Product Pillars to meet your every need Individually outstanding, unrivalled in combination With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial and factory automation.
General mounting, wire connection and disconnection. Troubleshooting the device. Repair of the device and replacement of circuit breakers must be done by PR electronics A/S only. Warning Do not open the front plate of the device as this will cause damage to the connector for the display / programming front PR 4500.
Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively, PR electronics A/S www.prelectronics.com The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
How to demount system 9000 Picture 1: By lifting the bottom lock, the device is detached from the DIN rail. Mounting the PR 4500 communication interfaces 1: Insert the tabs of the PR 4500 into the slots at the top of the device. 2: Hinge the PR 4500 down until it snaps into place.
Solenoid / alarm driver 9203 • Universal driver for solenoids, acoustic alarms and LEDs • Extended self-diagnostics • 1 or 2 channels • Can be supplied separately or installed on power rail, PR 9400 • SIL 2-certified via Full Assessment Advanced features •...
Applications - 9203Axxxx Output signals: Input signals: Channel 1 Channel 2* Alarm Solenoid Channel 1* * For full overview of input connections, refer to page 16. Power rail Status relay signal Rail, supply + Rail, supply - No connection No connection Channel 2 Power connection: Alarm...
Applications - 9203Bxxxx Output signals: Input signals: Channel 1 Channel 2* Alarm Solenoid Channel 1* * For full overview of input connections, refer to page 16. Power rail Status relay signal Rail, supply + Rail, supply - No connection No connection Channel 2 Power connection: Alarm...
Order Associated Type Output Channels Input I.S. / Ex approvals apparatus 9203 Low current : 1 Single Opto / switch ATEX, IECEx, FM, INMETRO, CCC, EAC-Ex, UKEX Double UL 913, ATEX, IECEx, FM, : -U9 INMETRO, CCC, EAC-Ex, UKEX High current : 2 Single KCs, ATEX, IECEx, FM, : -KCs...
Page 11
Max. power Max. required Type Description dissipation power 9203x1A-x 1 ch., low current ≤ 1.1 W ≤ 1.9 W 9203x1A1x 1 ch., low current ≤ 1.1 W ≤ 1.9 W 9203x1A2x 1 ch., low current ≤ 1.1 W ≤ 1.9 W 9203x1B-x 2 ch., low current ≤...
Output loads 9203x1Axx (1 channel) / 9203x1Bxx (2 channels) 41-42 / 51-52 41-43 / 51-53 41-44 / 51-54 Terminal Vout. no load Min. 24 V Min. 24 V Min. 24 V Vout. with load Min. 12.5 V Min. 13.5 V Min.
Page 13
9203x2Axx (1 channel) 41-42 41-43 41-44 Terminal Vout. no load Min. 24 V Min. 24 V Min. 24 V Vout. with load Min. 11.5 V Min. 9 V Min. 12.5 V Min. 10 V Min. 13.5 V Min. 11 V Iout.
Page 14
Relay output Status relay in safe area: Max. voltage ........125 VAC / 110 VDC Max.
Outputs - 9203xxxxx: Solenoid, ON / OFF Acoustic alarm Solenoid, ON / OFF Acoustic alarm Block diagram Power rail connections 91 92 93 94 95 Supply - Device status, Green ON Supply +24 VDC Ch. 1 status, OFF Yellow/Red Status relay N.C.
Signal error indications without display front List of LED and error signal indications Ch. 1: Ch. 2: Power rail Condition Green LED Status relay, N.C. Yellow / Red Yellow / Red signal status Device OK Flashing Energized No supply De-energized Device defective De-energized Ch.
Password protection: Programming access can be blocked by assigning a password. The password is saved in the device in order to ensure a high degree of protection against unauthorised modifications to the configuration. If the configured password is not known, please contact PR electronics support - www.prelectronics.com/contact. Signal and sensor error indication via display front PR 4500 The display front can be configured to show output status, output current (load) or tag no.
Routing diagram If no key is activated for 1 minute, the display will return to the default state 1.0 without saving configuration changes. 1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Save the chosen value and proceed to the next menu Hold 3 Back to previous menu / return to menu 1.0 without saving.
Help text overview [01] Set correct password [02] Enter advanced setup? [06] Enter language setup Enter password setup Enter display setup Enter SIL setup [07] Select direct channel function Select inverted channel function [09] Adjust LCD contrast [10] Adjust LCD backlight [11] Write a 5-character channel tag [12]...
9203QI01 LERBAKKEN 10, 8410 RØNDE DENMARK IECEx Installation drawing For safe installation of 9203 the following must be observed. The module shall only be Installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.
Page 24
9203QI01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Bxxx Installation: Hazardous area Non Hazardous area Zone 0, 1, 2, 20, 21, 22 or Zone 2 -20 ≤ Ta ≤ 60ºC 4501 Supply / Input (terminal 11,12,13,14) (terminal 31,32,33,34) (terminal 91,92,93,94,95) : 253 V, max. 400 Hz 9203B 91 92 93 94 95 Power...
Page 26
9203QI01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Axxx Installation Non Classified area or Zone 2 4501 9203A 91 92 93 94 95 Power Rail Terminal (31,32) Terminal (11,12 and 13,14) Supply: Input: Voltage 19.2 – 31.2 VDC Voltage Max. 28 VDC Power max.
For Installation in Zone 2 / Division 2 the following must be observed. The 4501 programming module is to be used solely with PR electronics’ modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust and moisture shall be installed.
Page 28
9203QA01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Bxxx Installation: Hazardous area Non Hazardous Area Zone 0,1,2, 20, 21, 22 or Z one 2 4501 -20 ≤ Ta ≤ 60ºC 9203B 91 92 93 94 95 Supply / Input Power (terminal 11,12,13,14) Rail (terminal 31,32,33,34) (terminal 91,92,93,94,95)
Page 30
9203QA01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Axxx Installation: Non Classified area or Zone 2 4501 9203A 91 92 93 94 95 Power Rail Terminal (31,32) Terminal (11,12 and 13,14) Supply: Input: Voltage 19.2 – 31.2 VDC Voltage max 28 VDC Power max.
9203QF01 LERBAKKEN 10, 8410 RØNDE DENMARK FM Installation drawing For safe installation of 9203 the following must be observed. The module shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number.
Page 32
9203QF01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Bxxx Installation: Hazardous Classified Location Unclassified Location or Class I/II/III, Division 1, Group A,B,C,D,E,F,G Hazardous Classified Location or Class I, Zone 0/1 Group IIC, [AEx ia] IIC Class I, Division 2, Group A,B,C,D T4 or Group IIC, [Ex ia Ga] IIC Gc or Class I Zone 2 Group IIC T4 Gc -20 ≤...
For Installation in DIV2/Zone2 the following must be observed. The 4501 programming module is to be used solely with PR electronics modules. It is important that the module is undamaged and has not been altered or modified in any way. Only 4501 modules free of dust...
Page 35
9203QU01 LERBAKKEN 10, 8410 RØNDE DENMARK Installation notes 9203Axxx-U9 and 9203Bxxx-U9 The module must be installed in a tool-secured enclosure suitable for the application in accordance with the National Electrical Code (ANSI/NFPA 70) for installation in the United States, the Canadian Electrical Code for installations in Canada, or other local codes, as applicable.
Page 36
9203QU01 LERBAKKEN 10, 8410 RØNDE DENMARK Installation notes 9203Bxxx-U9: Associated Equipment /Appareillage Associé [Ex ia] The Ex output current of this associated apparatus is limited by a resistor such that the output voltage-current plot is a straight line drawn between open-circuit voltage and short-circuit current. Selected intrinsically safe equipment must be third party listed as intrinsically safe for the application, and have intrinsically safe entity parameters conforming withTable 1 below.
Page 37
9203QU01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Bxxx-U9 Installation: Hazardous Classified Location Unclassified Location or Class I/II/III, Division 1, Group A,B,C,D,E,F,G Hazardous Classified Location Zone 0,1, 2 Group IIC, IIB, IIA or Class I, Division 2, Group ABCD T4 Zone 20, 21 Class I Zone 2 Group IIC T4 -20 ≤...
Page 38
9203QU01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203B1A-U9 9203B2A-U9 La, Lo Lo/Ro Ca, Co La, Lo Lo/Ro 9203B1B-U9 Terminal 41-42 Terminal 41-42/51-52 Voc, Uo IIC or A,B Voc, Uo IIC or A,B 80nF 4.15mH 54µH/Ω 80nF 2.69mH 44µH/Ω Isc, Io 93 mA IIB or C,E,F 640nF 16.6mH...
Page 39
9203QU01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Axxx-U9 and 9203Bxxx-U9 Installation: Non Hazardous area or Class I, Division 2, Group ABCD T4 or Zone 2 Group IIC T4 4501 -20 ≤ Ta ≤ 60ºC 9203A 91 92 93 94 95 Power Rail Terminal (31,32) Terminal (11,12 and 13,14)
9203QB01 LERBAKKEN 10, 8410 RØNDE DENMARK INMETRO Desenhos para Instalação Para instalação segura do 9203B o manual seguinte deve ser observado. O módulo deve ser instalado somente por profissionais qualificados que estão familiarizados com as leis nacionais e internacionais, diretrizes e normas que se aplicam a esta área. Ano de fabricação pode ser obtido a partir dos dois primeiros dígitos do número de série.
Page 41
9203QB01 LERBAKKEN 10, 8410 RØNDE DENMARK Área de não classificada Área de classificada Zona 0, 1, 2, 20, 21 e 22 ou Zona 2 -20 ≤ Ta ≤ 60ºC 4501 9203 Fonte / Entrada 91 92 93 94 95 (terminais 11,12,13,14) TRILHO DE ENERGIA (terminais 31,32,33,34) (terminais 91,92,93,94,95)
9203QI01 LERBAKKEN 10, 8410 RØNDE DENMARK IECEx 설 치 도 면 9203의 안 전 한 설 치 를 위 해 다 음 사 항 을 준 수 해 야 합 니 다 . 이 모 듈 은 이 지 역 에 적 용 되 는 국 내 및 국 제 법 률 , 지 침 및 표 준 에 정 통 한 유 자 격 자 만 설...
Page 44
9203QI01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Bxxx 설 치 : 위 험 지 역 비 위 험 지 역 구 역 0, 1, 2, 20, 21, 22 또 는 구 역 2 -20 ≤ Ta ≤ 60ºC 4501 공 급 / 입 력 (단...
Page 45
9203QI01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203B1A, 9203B1B 9203B2A Lo/Ro Lo/Ro 단 자 41-42/51-52 단 자 41-42 80nF 4.2mH 54µH/Ω 80nF 2.69mH 44µH/Ω 93 mA 640nF 16.8mH 218µH/Ω 115mA 640nF 10.8mH 176µH/Ω 0.65W 2.1µF 32.6mH 436µH/Ω 0.81W 2.1µF 20.8mH 353µH/Ω 3.76µF 32.6mH 436µH/Ω...
Page 46
9203QI01 LERBAKKEN 10, 8410 RØNDE DENMARK 9203Axxx 설 치 비 분 류 지 역 또 는 구 역 2 4501 9203A 91 92 93 94 95 Power Rail 단 자 (31,32) 단 자 (11,12 및 13,14) 공 급 : 입 력 : 19.2 –...
Document history The following list provides notes concerning revisions of this document. Rev. ID Date Notes 1707 Specifications for max. required power added. New INMETRO certificate and installation drawing. 1735 Connection drawings and block diagram updated. 1914 CCOE approval discontinued. 1949 Variant with UL 913 approval added.
Page 48
We are near you, all over the world Our trusted red boxes are supported wherever you are All our devices are backed by expert service and a 5-year business with a global reach. This means that we are warranty. With each product you purchase, you receive always nearby and know your local markets well.
Page 49
Benefit today from PERFORMANCE MADE SMARTER PR electronics is the leading technology company specialized in making industrial process control safer, more reliable and more efficient. Since 1974, we have been dedicated to perfecting our core competence of innovating high precision technology with low power consumption.