Download Print this page
E2S E2xL15UL Instructions/Service Manual

E2S E2xL15UL Instructions/Service Manual

Advertisement

Quick Links

15 Watt Loudspeaker
70V or 100V Line Transformer
with 15W, 7.5W, 3W and 1W tapings
8 ohm or 16 ohm
Type 4 / 4X / 13
Operating Temperature Range
-20ºC to +55ºC
Unit Type No.
E2xL15UL
Impedance:
8 ohm or 16 ohm
70V Line or 100V Line
Max. Operating Temperature / Code at +55ºC Ambient
Hazardous Location
Class I, Division 2, Groups A, B, C, D
Class II, Division 2, Groups F and G
Class III, Divisions 1 and 2
Max. Operating Temperature / Code at +40ºC Ambient
Hazardous Location
Class I, Division 2, Groups A, B, C, D
The equipment is suitable for use in the hazardous locations
listed above or non-hazardous locations only.
PRE-INSTALLATION
WARNING –
The E2xL15UL loudspeakers are supplied with
flying leads so it should not be necessary to open the unit
before it is installed.
M4 Hex
Socket Screw
Spring Washer
Flat Washer
WARNING – DO NOT OPEN WHEN ENERGISED
CAUTI0N - DO NOT OPEN WHEN AN EXPLOSIVE GAS
OR DUST ATMOSPHERE IS PRESENT
MOUNTING
The E2xL15UL loudspeaker must be mounted using the
rotating bracket as shown.
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. IS4211
Issue: D
INSTRUCTION & SERVICE MANUAL
E2xL15UL LOUDSPEAKERS
For Use In Hazardous Locations
7KA1
Temperature Code
T4 (135ºC)
T6 (85ºC)
T6 (85ºC)
Temperature Code
T4A (120ºC)
19-06-07
Sheet 1 of 2
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS I, II DIVISION 2.
WIRING INSTALLATION
The E2xL15ULUL loudspeaker has one ½ NPT cable entry, the
blanking plug adjacent to the cable entry is permanently fixed
and must not be removed. The sounder is pre-wired with flying
leads which are colour coded and should be connected as
shown in the diagram below.
The conduit running from the supply to the sounder must
include an equipment grounding conductor that is at earth
potential to facilitate ground connection of the device. A number
of loudspeakers can be connected in a chain to the same
supply using field installed wiring compartments that are
appropriate for the hazardous location, provided that the
conductor at earth potential can be readily connected to the
ground lead on each loudspeaker in the chain.
WARNING - ALL ELECTRICAL WIRING MUST BE
INSTALLED IN ACCORDANCE TO THE
NATIONAL ELECTRICAL CODE
100V and 70V Loudspeakers
White
Common
Red
15 Watts
Orange
7.5 Watts
Yellow
3 Watts
Violet
1 Watt
Green/Yellow
Ground
Watts
C
15
7,5
3
Comman
15 Watts
7.5 Watts
3 Watts
1 Watt
NOTE - All wires are not used they must be individually insulated to ensure that
cannot make contact to any other wires.
sales@e-2-s.com
www.e-2-s.com
18° Increments
Release nut to rotate
bracket.
Watts
1
C
15
7,5
3
1
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200
Watts
C
15
7,5
3
1

Advertisement

loading

Summary of Contents for E2S E2xL15UL

  • Page 1 7.5 Watts 3 Watts 1 Watt MOUNTING The E2xL15UL loudspeaker must be mounted using the NOTE - All wires are not used they must be individually insulated to ensure that rotating bracket as shown. cannot make contact to any other wires.
  • Page 2 Comman 15 Watts POWER AMPIFIER SELECTION It is important that the E2xL15UL loudspeakers are connected to power amplifiers that have outputs that are compatible to the type of loudspeaker being used. Loudspeakers with a 70V or 100V line matching transformer fitted must be connected to a power amplifier with a 70V or 100V line output.