7. Clearance of the HEATFLOW S5 to combustible material
The HEATFLOW S5 can only be assembled with a single wall pipe, refer to the Annex for double
wall pipe retrofit.
The HEATFLOW S5 cannot be assembled with a Heat shield (AC02762), lowered ceiling, inside
an alcove or in a mobile home.
The following clearances for stoves with the HEAFLOW S5 must be respected, failure to do so may result in
damage to the stove, air ducts, blower and may also cause a fire.
The HEATFLOW S5 CANNOT BE INSTALLED IN REDUCED CLEARANCES
It is absolutely essential to place the stove to gain clearance for combustible material from the jacket.
The following clearances for the stoves with the HEAFLOW S5 must be respected
JACKET CLEARANCE WITH SINGLE WALL
PIPE CONNECTOR
CANADA
A
14 ½" (368mm)
B
12 ½" (318mm)
C
10" (254mm)
Installation Instruction HEATFLOW S5
WARNING
USA
14 ½" (368mm)
12 ½" (318mm)
10" (254mm)
English
DISTANCE FROM PIPE CONNECTOR
WITH SINGLE WALL PIPE CONNECTOR
CANADA
D
18" (457mm)
E
22 ¾" (578mm)
F
19 3/4" (502mm)
14
USA
18" (457mm)
22 ¾" (578mm)
19 3/4" (502mm)
46310A
2023-03-15