RPL75 - product 2- PRODUCT 1. Anticondensation fi lter 2. M20 skintop 3. VL601 (opt.) 4. Sensor IDENTIFICATION Each meter has an adhesive identifi cation plate on which are indicated the meter main data. The following picture describes the information on the identifi cation plate.
RPL75 - features 3-FEATURES Housing/sensor material PC / PP wetted part Mechanical installation 2” GAS M (Flange in PP DN80 (opt.) Protection degree IP67/IP68 (Antenna) Electrical connection Internal push connectors Working temperature -20 ÷ +60°C Pressure Max. 3 bar Power supply 20÷30Vdc...
RPL75 - installation 5-INSTALLATION 5.1 MOUNTING PRECAUTIONS 5.1.1 Mounting position - Leave a 300mm (d) minimum distance between the sensor and the tank smooth wall. - Use a protective cover to protect the sensor from weather and direct sunlight (c).
Page 8
RPL75 - installation 5.1.3 Blind distance During installation is important to remember that in the sensor proximity there is a blind zone (or BLIND DISTANCE) of 0.05m where the sensor can not measure. 0.05 Min. Blind Distance 5.1.4 Installation in nozzle In case of nozzle installation, make sure the sensor bottom protrudes at least 10mm from the bottom of the nozzle.
Page 9
The level measurement is possible thanks to the Auto-Tuned statistical fi lter. Should rarely need to adjust the fi lter setting by editing 2 RPL75 sensor programming parameters: - FILTER; this parameter is present in the Quick Setup menu and in the Advanced Confi guration “SETUP” menu;...
RPL75 - electrical connections 6-ELECTRICAL CONNECTIONS 6.1 WIRING 1) Separate the engine control cables or power cables from the RPL75 connection cables. 2) Open the cap by unscrewing. 3) Lead the cables into the transmitter through the glands. 4) Do not use sleeves terminals, because they might interfere with the VL601 module insertion.
3) MODBUS RTU communication S/W, cod.010F105A, for RPL75 transmitter. With this so! ware is possible: - to connect the RPL75 transmitters in MODBUS RTU network by selecting the UID address. - to read on your PC monitor all measures in reading and RPL75 operation data.
Displayed at the top alerts that there is a generic error; press SCROLL to show the message that indicates the present error type. The RPL75 returns automatically to RUN mode. QUICK SETUP - Menu with easy access for quick basic parameters confi guration.
RPL75 - quick setup 9-QUICK SETUP 9.1 - Quick Setup menu structure Para ¥ ¥ ¤ ¥ ¨ ¨ ¥ ¦ Set Distance 4 I ! ! ! ! ...
Page 16
RPL75 - quick setup 9.2.1 SET DISTANCE 4mA SET DISTANCE 4mA SET DISTANCE 20mA MAX DISTANCE Press ENTER to display the distance value associated with 4mA output. FILTER COEFFICENT BLIND DISTANCE DISPLAY RL1 THRESHOLD RL2 THRESHOLD SET DISTANCE 4mA Use SCROLL and UP ARROW to modify that value;...
Page 17
RPL75 - quick setup 9.2.3 MAX DISTANCE SET DISTANCE 4mA SET DISTANCE 20mA MAX DISTANCE Press the ENTER key to display the previously set maximum distance value. FILTER COEFFICENT The MAX DISTANCE is used to prevent the sensor from detecting an echo signal BLIND DISTANCE at a distance .
Page 18
RPL75 - quick setup 9.2.4 FILTER COEFFICIENT SET DISTANCE 4mA SET DISTANCE 20mA MAX DISTANCE Press ENTER. FILTER COEFFICENT Use SCROLL and UP ARROW to modify the value. BLIND DISTANCE Input a value from 1 to 99. DISPLAY 1 maximum speed, 99 maximum slowness.
Page 19
RPL75 - quick setup 9.2.5 BLIND DISTANCE SET DISTANCE 4mA SET DISTANCE 20mA MAX DISTANCE Press ENTER. FILTER COEFFICENT The BLIND ZONE is used to avoid undesired measures near the transmitter. BLIND DISTANCE DISPLAY RL1 THRESHOLD RL2 THRESHOLD Use SCROLL and UP ARROW to modify the value.
Page 20
RPL75 - quick setup 9.2.7 RL1 THRESHOLD SET DISTANCE 4mA SET DISTANCE 20mA MAX DISTANCE Press ENTER to display the previous setting. FILTER COEFFICENT Set the distance from the sensor. BLIND DISTANCE DISPLAY RL1 THRESHOLD RL2 THRESHOLD Use SCROLL and UP ARROW to modify the value;...
Page 21
NB - RL2 inactive with 0000mm When confi rming with the ENTER button the maximum level threshold value storage, in the example 3000mm, the RPL75 activates RL2 with the following default settings for level alarm threshold: 1) MIN / MAX = MAX; maximum distance alarm.
RPL75 - advanced confi guration 10-ADVANCED CONFIGURATION 10.1 - “SETUP” MENU SET DISTANCE 4mA 0000mm SETUP SET DISTANCE 4mA SET DISTANCE 20mA 0000mm SET DISTANCE 20mA MAX DISTANCE MAX DISTANCE 00000mm FILTER COEFFICIENT VALUE FILTER COEFFICENT 0000mm BLIND DISTANCE BLIND DISTANCE...
Page 23
RPL75 - advanced confi guration 10.2.1 - SET DISTANCE 4mA SET DISTANCE 4mA SET DISTANCE 20mA MAX DISTANCE Position the cursor on DISTANCE 4mA, press ENTER to access. FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV. 4mA ACTUAL LEV. 20mA RELAYS Use UP ARROW and SCROLL to modify the value.
Page 24
RPL75 - advanced confi guration 10.2.5 - BLIND DISTANCE SET DISTANCE 4mA SET DISTANCE 20mA MAX DISTANCE Position the cursor on DISTANCE 4mA, press ENTER to access. FILTER COEFFICIENT Represent the “BLIND ZONE”. BLIND DISTANCE ACTUAL LEV. 4mA ACTUAL LEV. 20mA...
Page 25
RPL75 - advanced confi guration 10.2.8 - RELAYS SET DISTANCE 4mA SET DISTANCE 20mA MAX DISTANCE Position the cursor on RELAYS, press ENTER to access. FILTER COEFFICIENT BLIND DISTANCE ACTUAL LEV. 4mA ACTUAL LEV. 20mA RELAYS In this sub-menù itʼs possible to setup onboard relays RL1 can be set as threshold relay or pump-control relay;...
Page 26
RPL75 - advanced confi guration 10.2.8.1.3 - DELAY VALUE MIN/MAX Position the cursor on DELAY, press ENTER to access. DELAY SAFETY ANABLE/DISABLE MIN/MAX HYSTERESIS Itʼs possible to set the activation delay for the selected relay, from 0 to 99 sec.
Page 27
RPL75 - advanced confi guration 10.2.8.2 - RL1 PUMP (only for RL1) RL1 THRESHOLD Position the cursor on RL1 PUMP, press ENTER to access RL2 THRESHOLD RL1 PUMP A pump control functioning activation, with hysteresis, is possible two thresholds setting is required:...
Page 28
RPL75 - advanced confi guration 10.2.8.2.3 - DELAY UPPER Position the cursor on DELAY, press ENTER to access. LOWER DELAY FILL./EMPT. ENABLE/DISABLE Set the relay delay activation, from 0 to 99 sec. Use UP ARROW and SCROLL to modify the value.
Page 29
RPL75 - advanced confi guration 10.3 “DISPLAY” menu DISTANCE mm >1 VALUE DISPLAY DISPLAY VALUES LEVEL mm 2 VALUES LEVEL % OUTPUT mA 1 VALUE >2 VALUES >PRIMARY VALUE DISTANCE mm SECONDARY VALUE LCD CONTRAST LIVEL mm LCD CONTRAST LIVEL %...
Page 30
Position the cursor on WELCOME TEXT, press ENTER to access. WELCOME TEXT Itʼs possible to edit or delete the message that is displayed by the RPL75 during the ignition phase. Use UP ARROW (up scroll) and SCROLL (down scroll) to change the digit;...
Page 31
RPL75 - advanced confi guration 10.5 “DIAGNOSTIC” menu NO ECHO FOUND DISABLE DIAGNOSTIC ECHO IN BLIND ALARM CONFIGURATION >ENABLE DISTANCE >120% MEASURE STATUS 00.00 PEAK VALUES >DISPLAY VALUES PEAK VALUES Max 0000mm RESET VALUES Min 0000mm OUTPUT SIMUL OUTPUT SIMUL 00.0mA...
Page 32
RESET VALUES Displays the max. and min. distance measured from power on. LEFT ARROW to exit. PEAK VALUES NB - The peak values stored are erased every time the RPL75 turns-off 0000mm 0000mm 10.6.3.2 - RESET VALUES Position the cursor on RESET VALUES, press ENTER to access.
Page 33
RPL75 - advanced confi guration 10.6.5 - LOW DK FILTER ALARM CONFIGURATION MEASURE STATUS In level measurement applications with products having a low dielectric PEAK VALUES constant value (e.g. oils), the radar pulses can pass through the product and OUTPUT SIMUL.
Page 34
RPL75 - advanced confi guration 10.7 “SERVICE” menu 21.5 mA 3.85 mA SERVICE OUTPUT SAFE MODE >HOLD LAST VALUE SET UID SET UID ENGLISH >ITALIANO LANGUAGE FRANCAIS F_WINDOW F_WINDOW RESTORE SETTINGS OK TO CONFIRM BLUETOOTH CANGE DEVICE PIN RESET MODULE 10.8 - SERVICE...
Page 35
Example: F_WINDOW parameter set to 5. SET WIDTH - The RPL75 detects an echo signal which is 4 meters from the sensor. - Suddenly, the echo signal disappears and a new echo signal to 3.5 mt away from the sensor is detected.
Page 36
LANGUAGE F_WINDOW RESTORE SETTING BLUETOOTH Press ENTER to restore the RPL75 default settings. LEFT ARROW to exit without restored the RPL75 default settings OK TO CONFIRM 10.8.6 - BLUETOOTH (OPTIONAL) OUTPUT SAFE MODE SET UID Position the cursor on BLUETHOOT, press ENTER to access.
Page 37
RPL75 - info 10.9 “INFO” menu SGM-LEKTRA RPL75 INFO FIRMWARE REV. 10.9.1 - INFO SETUP DISPLAY Position the cursor on INFO, press ENTER to access. DIAGNOSTIC SERVICE INFO SGM-LEKTRA In addition to information about the manufacturer, are displayed the RPL75 fi...
Documentation subject to technical change with no prior warning 12-FACTORY TEST AND QUALITY CERTIFICATE In conformity to the company and check procedures I certify that the equipment: (Radar level transmitter) is conform to the technical requirements on Technical Data and it is made in conformity to the procedure Quality Control Manager: ............